48
ENG
Heos +0300078EN - rel. 1.6 - 23.11.2017
Mask index Par. Description Default UOM Min Max Possible value descr. R/W
Eb08 P15 Off set on control T when LP probe is broken or discon-
nected
3.0 (5.4) °C (°F) 0 (0) 68.0 (122.4) R/W
Ec01 /7 Type of showcase display 0 -- 0 1
0: PLD WITH BUTTONS
1: PLD DISPLAY
R/W
/t2 Value shown on showcase display 12 -- 0 13
0: NONE
1: U01, ..., 10: U10
11: REGULATION PROBE
12: VIRTUAL PROBE
13: SETPOINT
R/W
Ec02 /t Enable show alarms on showcase display 1 -- 0 1
0: NO; 1: YES
R/W
d6 Display management during defrost 0 -- 0 2
0: VALUE TEMP. AND DEF
1: VALUE TEMP. FROZEN
2: ALWAYS DEF
R
H4 Enable buzzer 1 -- 0 1
0: NO; 1: YES
R/W
Ec03 Ut Temperature unit of measure 0 -- 0 1
0: °C; 1: °F
R/W
UP Pressure unit of measure 0 -- 0 1
0: BARG
1: PSIG
R/W
Ec04 Select language used on pGDe 1 -- 1 2
0: ITALIAN
1: ENGLISH
R/W
Ed02 cLK Clock "hour" setting 0 h 0 23 R/W
Clock "minutes" setting 0 -- 0 59 R/W
Clock "day" setting 0 -- 1 31 R/W
Clock "month" setting 0 -- 1 12 R/W
Clock "year" setting 0 -- 0 99 R/W
Read current day of the week 0 -- 0 0
0: ***
1: MONDAY
2: TUESDAY
3: WEDNESDAY
4: THURSDAY
5: FRIDAY
6: SATURDAY
7: SUNDAY
R
Ed03 cKu Type of clock update 0 -- 0 1
0: FROM BMS
1: FROM MASTER.
R/W
Ee01 Y0 User password 000 -- 0 999 R/W
Y1 Service password 123 -- 0 999 R/W
Y2 Manufacturer password 123 -- 0 999 R/W
Ee02 PP Login Password 0 -- 0 999 R/W
Ee03 PD Menu access time without re-entering password 15 min 0 90 R/W
Ef01 Y3 Install Carel default parameters 0 -- 0 1
0:
1: DEFAULT. INSTALLATION
R/W
Ef02 Save confi guration 0 -- 0 1
0:
1: SAVE
R/W
Ef03 Load the saved confi guration 0 -- 0 1
0:
1: SAVE
R/W
Ef04 Delete previous confi guration 0 -- 0 1
0:
1: DELETE
R/W
Fc01 Aa Select probe for high and low temperature alarm Al.1 1 -- 0 9
0: VIRTUAL PROBE
1: OUTLET PROBE
2: DEFROST PROBE
3: INTAKE PROBE
4: SUCTION PROBE
5: SATURATION PROBE
7: AUX.1 PROBE
8: AXU.2 PROBE
9: TEMP.DEWP.PROBE
R/W
AH High temperature alarm threshold Al.1 10.0 (50.0) °C (°F) -50.0 (-58.0) 50.0 (122.0)
if A1= 1: ABSOLUTE
R/W
10.0 (18.0) °C (°F) 0.0 (0.0) 50.0 (90.0)
if A1= 0: RELATIVE
AL Low temperature alarm threshold Al.1 4.0 (39.2) °C (°F) -50.0 (-58.0) 50.0 (122.0)
if A1= 1: ABSOLUTE
R/W
4.0 (7.2) °C (°F) 0.0 (0.0) 50.0 (90.0)
if A1= 0: RELATIVE
A1 Type of alarm thresholds, relative to control set point or
absolute
0-- 0 1
0: RELATIVE
1: ABSOLUTE
R/W
Fc02 A0 Temperature alarm diff erential 2.0 (3.6) °C (°F) 0,1.0 (0,18.0) 20.0 (36.0) R/W
Ad High and low temperature alarm delay 120 min 0 240 R/W
Fc03 Ar Enable alarm propagation from Slaves to Master 0 -- 0 1
0: NO; 1: YES
R/W
A7 Delay time for delayed external alarm 1 min 0 240 R/W
Fc04 Aa2 Select probe for high and low temperature alarm Al.2 0 -- 0 9
0: VIRTUAL PROBE
1: SOUTLET PROBE
2: DEFROST PROBE
3: INTAKE PROBE
4: SUCTION PROBE
5: SATURATION PROBE
7: AUX.1 PROBE
8: AXU.2 PROBE
9: TEMP.DEWP.PROBE.
R/W
AH2 High temperature alarm threshold Al.2 10.0 (50.0) °C (°F) -50.0 (-58.0) 50.0 (122.0)
se A1= 1: ABSOLUTE
R/W
10.0 (18.0) °C (°F) 0.0 (0.0) 50.0 (90.0)
se A1= 0: RELATIVE
AL2 Low temperature alarm threshold Al.2 4.0 (39.2) °C (°F) -50.0 (-58.0) 50.0 (122.0)
se A1= 1: ABSOLUTE
R/W
4.0 (7.2) °C (°F) 0.0 (0.0) 50.0 (90.0)
se A1= 0: RELATIVE
A2 Type of alarm thresholds, relative to control set point or
absolute
0-- 0 1
0: RELATIVE
1: ABSOLUTE
R
Fc05 AdE Alarm delayed external delay priority 0 -- 0 1
0: LOW
1: HIGH
R/W
As Serial probe alarm delay 30 min 10 500 R/W
Fd00 rF Reset alarm log 0 -- 0 1
0: NO; 1: YES
R/W
Tab. 7.al
These parameters can only be set by Carel HQ, depending on the compressor model. Changing the settings may aff ect compressor life, as they have been agreed
on with the compressor manufacturer. For any settings, please contact Carel.