48
humiSteam - cod. +030221914 rel. 5.2 - 07.11.2005
parameters for configuring the operation of accessory devices
code range of def. unit of description
disp. variation measure
b1 0, …, 31 0 see Tab. 7.3.3 (Functions of the parameter b1)
b2 0, …,120 0 s shut-down delay time
b3 -10.0, …,10.0 0.0 % current measurement gain
b4 0, ..., 199 water conductivity (0=automatic measurement)
0k2, ….2k0 0 µS/cm
b5 0, …, 199 conductivity pre-alarm threshold
0k2, ….2k0 1k5 µS/cm
b6 0, …, 199 conductivity alarm threshold
0k2, …, 2k0 2k0 µS/cm
b7 0, …, 100 50 % foam detection threshold (0=exclude foam detect, 1=max sens., 100=min sens.)
b8 50, …, 200 100 % internal conductivity reached by the cylinder in stable conditions against rated value
b9 50, ..., 200 100 % adjust the duration of the drain for dilution
bb 0*, ..., 4000 1500 h cylinder maintenance limit time (in hours)
0*= excluding life alarm “Cy” and the obligatory maintenance alarm “Mn”
100 hour step if bb>199 hours, hour step if bb<199 hours
bE 1, ..., 120 24 h time limit between two periodical drain accessible only if periodical draining is enabled
cycles (weight 64 in “b1”)
bF 1, ..., 199 3 days days to wait to drain due to inactivity not accessible if draining due to
inactivity is disabled, weight 8 in “b1”
Table. 7.3.2
humiSteam - Parameter b1
FUNCTIONS
b1 DE-HUMIDIFICATION DILUTION DRAIN WITH DRAIN WHEN NEW DEMAND TOTAL DRAIN FOR DISPLAY OF ALARM RELAY TOTAL PERIODICAL
REQUEST CONTACTOR … <= 2/3 CURRENT DEMAND INACTIVITY WARNINGS “CL & “CP” ACTIVATED WHEN… DRAIN
(CONTACTOR OPENED)
DEF. 0 OFF OPEN YES ON, depending on bF ON ALARMS PRESENT OFF
1 ON OPEN YES ON, depending on bF ON ALARMS PRESENT OFF
2 OFF CLOSED YES ON, depending on bF ON ALARMS PRESENT OFF
3 ON CLOSED YES ON, depending on bF ON ALARMS PRESENT OFF
4 OFF OPEN NO ON, depending on bF ON ALARMS PRESENT OFF
5 ON OPEN NO ON, depending on bF ON ALARMS PRESENT OFF
6 OFF CLOSED NO ON, depending on bF ON ALARMS PRESENT OFF
7 ON CLOSED NO ON, depending on bF ON ALARMS PRESENT OFF
8 OFF OPEN YES OFF ON ALARMS PRESENT OFF
9 ON OPEN YES OFF ON ALARMS PRESENT OFF
10 OFF CLOSED YES OFF ON ALARMS PRESENT OFF
11 ON CLOSED YES OFF ON ALARMS PRESENT OFF
12 OFF OPEN NO OFF ON ALARMS PRESENT OFF
13 ON OPEN NO OFF ON ALARMS PRESENT OFF
14 OFF CLOSED NO OFF ON ALARMS PRESENT OFF
15 ON CLOSED NO OFF ON ALARMS PRESENT OFF
16 OFF OPEN YES ON, depending on bF OFF ALARMS PRESENT OFF
17 ON OPEN YES ON, depending on bF OFF ALARMS PRESENT OFF
18 OFF CLOSED YES ON, depending on bF OFF ALARMS PRESENT OFF
19 ON CLOSED YES ON, depending on bF OFF ALARMS PRESENT OFF
20 OFF OPEN NO ON, depending on bF OFF ALARMS PRESENT OFF
21 ON OPEN NO ON, depending on bF OFF ALARMS PRESENT OFF
22 OFF CLOSED NO ON, depending on bF OFF ALARMS PRESENT OFF
23 ON CLOSED NO ON, depending on bF OFF ALARMS PRESENT OFF
24 OFF OPEN YES OFF OFF ALARMS PRESENT OFF
25 ON OPEN YES OFF OFF ALARMS PRESENT OFF
26 OFF CLOSED YES OFF OFF ALARMS PRESENT OFF
27 ON CLOSED YES OFF OFF ALARMS PRESENT OFF
28 OFF OPEN NO OFF OFF ALARMS PRESENT OFF
29 ON OPEN NO OFF OFF ALARMS PRESENT OFF
30 OFF CLOSED NO OFF OFF ALARMS PRESENT OFF
31 ON CLOSED NO OFF OFF ALARMS PRESENT OFF
32 OFF OPEN YES ON, depending on bF ON ALARMS ABSENT OFF
33 ON OPEN YES ON, depending on bF ON ALARMS ABSENT OFF
34 OFF CLOSED YES ON, depending on bF ON ALARMS ABSENT OFF
35 ON CLOSED YES ON, depending on bF ON ALARMS ABSENT OFF
36 OFF OPEN NO ON, depending on bF ON ALARMS ABSENT OFF
37 ON OPEN NO ON, depending on bF ON ALARMS ABSENT OFF
38 OFF CLOSED NO ON, depending on bF ON ALARMS ABSENT OFF
39 ON CLOSED NO ON, depending on bF ON ALARMS ABSENT OFF
40 OFF OPEN YES OFF ON ALARMS ABSENT OFF
41 ON OPEN YES OFF ON ALARMS ABSENT OFF
42 OFF CLOSED YES OFF ON ALARMS ABSENT OFF
43 ON CLOSED YES OFF ON ALARMS ABSENT OFF
44 OFF OPEN NO OFF ON ALARMS ABSENT OFF
45 ON OPEN NO OFF ON ALARMS ABSENT OFF
46 OFF CLOSED NO OFF ON ALARMS ABSENT OFF
47 ON CLOSED NO OFF ON ALARMS ABSENT OFF
48 OFF OPEN YES ON, depending on bF OFF ALARMS ABSENT OFF
49 ON OPEN YES ON, depending on bF OFF ALARMS ABSENT OFF
50 OFF CLOSED YES ON, depending on bF OFF ALARMS ABSENT OFF
51 ON CLOSED YES ON, depending on bF OFF ALARMS ABSENT OFF
Continues...