humiSteam - cod. +030221914 rel. 5.2 - 07.11.2005
6 slow E101 internal memory error 1. reset the default parameters total machine reprog. active reprog.
flashes (see Chap. 7.5) shut- disabled by CAREL by
CAREL
or 4 fast 2. if the problem persists, contact the CAREL down
flashes service centre
red
LED
Not E112 error in the parameters user 1. with the machine off check that there - machine reprog. active reprog.
featured are no defective electrical connections disabled params. params.
or faults, then reprogram the parameters
2. reset the default parameters
(see Chap. 7.5)
3. if the problem persists, contact the CAREL
service centre
Not E130 hour counter error with the machine off check that there are - hour reset not -
featured no defective electrical connections or counter manual active
faults, then reset the hour counter saving hour
(see par. 7.6) disabled counter
not E120 room probe not connected check the connection of the probe, - machine manual active auto
featured parameter A2 for the room probe and the disabled
setting of parameter A0 (see chap. 7)
not E123 outlet probe not connected check the connection of the probe, - signal manual active auto
featured parameter A6 for the outlet probe and the only
setting of parameter A0 (see chap. 7)
not E132 cylinder being depleted signal perform maintenance and/or replace the - signal manual not auto
featured cylinder only active
2 slow E133 cylinder depleted signal perform maintenance and/or replace the signal signal not not -
flashes cylinder only only available active
red LED
9 slow E134 cylinder full with machine off with the machine off: total machine manual active manual
flashes signal 1. check for any leaks from the fill shut- disabled
red LED electrovalve or the condensate return down
pipe
2. check that the level sensors are clean
total shut-down
not - cleaning cylinder started signal see paragraph 6.2.1 - - - - -
featured
not E135 timeout signal (see parameter perform maintenance and/or replace - signal manual active after the
envisaged bb”) for maintenance the cylinder only reset manual
exceeded hour reset
counter ** hour
counter
not E136 reached final limit (1.5xbb) replace the cylinder - disable manual active after the
envisaged of cylinder operating life unit reset manual
hour reset
counter ** hour
counter
not - complete draining of the see paragraph 6.3.2.6 - - - - -
envisaged cylinder activated
not - complete draining for see paragraph 11.4.5 - - - - -
envisaged extended inactivity
not - complete periodical see paragraph 11.4.9 - - - - -
envisaged draining active
not - anti-foam algorithm see paragraph 11.4.3 - - - - -
envisaged active
Table. 10.3.1
* CAREL Humivisor (H or T)
** it is recommended to replace the cylinder first
Note: for the P controllers the alarms cannot be reset. If the alarm is no longer active, it can only be reset by switching the machine off.
code displayed
controller remote causes solution action reset alarm reset
term.* display (H) relay relay (H)
PH PH