Carel m chiller - Compressor Parameters (c)

Carel m chiller
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21
d5 Tempo minimo per inizio sbrinamento U 10 150 sec 10 10 D--S-
Min. time-interval to start a defrosting cycle
d6 Durata minima sbrinamento U 0 150 sec 10 0 D--S-
Min. duration of a defrosting cycle
d7 Durata massima sbrinamento U 1 15 min 1 5 D--S-
Max. duration of a defrosting cycle
d8 Ritardo tra due richieste sbrinamento U 10 150 min 10 30 D--S-
nello stesso circuito /
Time-delay between
2 defrosting cycles within the same circuit
d9 Ritardo sbrinamento tra i 2 circuiti U 0 150 min 10 10 D--SB
Defrosting time-interval between the 2 circuits
dA Sbrinamento da contatto esterno F 0 1 flag 1 0 D--S-
Defrost end by external contact
db Resistenze antigelo in sbrinamento U 0 1 flag 1 0 D--S-
Antifreeze heaters activated while defrosting
dc Tempo di attesa prima dello sbrinamento F 0 3 min 1 0 D--S-
Delay before defrosting
dd Tempo di attesa dopo lo sbrinamento F 0 3 min 1 0 D--S-
Delay after defrosting
dE Fine sbrinamento con 2 circuiti frigoriferi F 0 1 flag 1 0 D--SB
ed 1 circuito ventilazione /
End defrosting
with 2 refrigerating circuits and 1 removal fan
ANTIGELO / RESISTENZA APPOGGIO Tipo Min. Max. U.M. Variazione Default Pres. DVNP Nuovo
ANTIFREEZE / SUPPORTING HEATERS Type Min. Max M.U. Variation Def. Presence New
A1 Set allarme antigelo/Bassa temperatura U -30 A4 °C 0.1 3.0 -----
ambiente (ARIA/ARIA) /
Antifreeze/Low
-22 A4 °F
ambient temp. (AIR/AIR) alarm set-point
A2 Differenziale allarme antigelo/bassa U 0.1 11.0 °C 0.1 5.0 -----
temperatura ambiente (ARIA/ARIA) 0.1 19.8 °F
Differential for antifreeze/Low ambient
temperature alarm
A3 Tempo bypass allarme antigelo/bassa U 0 150 sec 10 0 -----
temperatura ambiente all'accensione
della macchina in Inverno
Bypass time for antifreeze alarm/Low
ambient temperature when turning on
the unit in heating mode
A4 Set resistenza antigelo/appoggio U A1 rd °C/°F 0.1 5.0 -----
S
et point for the activation of antifreeze
heater/supporting heater
A5 Differenziale resistenza antigelo/appoggio U 0.1 11.0 °C 0.1 1.0 -----
Diff. for antifreeze heater/supporting heater
0.1 19.8 °F
A6 Sonda resistenze di appoggio F 0 1 flag 1 0 -----
Supporting heaters probe
ALLARME Tipo Min. Max. U.M. Variazione Default Pres. DVNP Nuovo
ALARM Type Min. Max M.U. Variation Def. Presence New
P1 Ritardo allarme flussostato U 0 150 sec 10 20 -----
all'avviamento pompa /
Flowswitch alarm
delayed when starting the pump
P2 Ritardo allarme flussostato a regime U 0 90 sec 1 5 -----
Flowswitch alarm delayed during normal
operating
P3 Ritardo allarme bassa pressione U 0 150 sec 1 40 -----
alla partenza compressore
Low pressure alarm delayed at compr. start-up
P4 Attivazione del cicalino /
Buzzer ON
U 0 15 min 1 0 -----
P5 Rispristino allarmi /
Reset of alarms
F 0 1 flag 1 0 -----
P6 set di param. /
2nd set of param.
F 0 1 flag 1 0 -----
P7 Allarme di bassa pressione con sonde F 0 1 flag 1 0 --CS-
di pressione /
Low pressure alarm with
pressure probes