6
“Power+” +0500048IE - rel 2.2 - 06.11.2014
ENG
2. INTRODUCTION
Power+ is a drive designed to control compressors with sensorless-brushless permanent magnet motors (BLDC/
BLAC) or asynchronous induction motors. The drives can also be used in some applications with fans and pumps,
and consequently the device off ers fl exible use in the air-conditioning and refrigeration sectors. It is fi tted for panel
installation or with heat sink outside of the panel. Confi guration and programming, as well as the run/stop controls and
speed reference, are managed by a CAREL pCO controller or any controller device via RS485 serial connection using the
Modbus® protocol in master mode.
2.1 Functions and main features
In summary:
compact dimensions for assembly in electrical panels;
operation at ambient temperatures from -20 to 60°C;
can be installed in residential and industrial environments;
connection via serial network to Master programmable controller;
network address can be confi gured by setting the dipswitches inside to the drive;
can control various types of compressors;
safety digital input (Safe Torque O );
dedicated input for PTC thermistor or thermostat to monitor motor overtemperature;
panel installation or with heat sink outside of the panel, to optimise the dissipation of heat inside the electrical
panel;
electrical connections can be made without needing to remove the plastic cover;
programmable acceleration curve to adapt to the required specifi cations when starting compressor;
high switching frequency to limit motor noise;
detailed information on drive status via numerous read-only variables;
protection functions for the drive (short-circuit, overcurrent, earth fault, overvoltage and undervoltage on the bus,
overtemperature), motor (overtemperature and limitation of current delivered) and system (Safe Torque O input,
communication failure).
Coldplate models to be thermal coupled to an auxiliary cooling device;
2.2 Models
Code Power supply Nominal output current (A) Frame size (*)
PSD1012200
PSD10122A0
200 - 240Vac ± 10%, 1~ 12
1
2
PSD1016200
PSD10162A0
200 - 240Vac ± 10%, 1~ 16
1
2
PSD1024400
PSD10244A0
380 - 480Vac ± 10%, 3~ 24
1
2
PSD1018400
PSD10184A0
380 - 480Vac ± 10%, 3~ 18
1
2
Tab. 2.a
(*) For the dimensions see par. 3.3. (size 1) and par. 3.10 (size 2 - Coldplate models).
2.3 Accessories
Code Description
PSACH10200 DC Choke for PSD10184*0 and PSD10244*0
Tab. 2.b