20
“Power+” +0500048IE - rel 2.2 - 06.11.2014
ENG
3.12 EMI lter (PSD10**2**)
The EMI fi lter is an optional that can be supplied separately to be used with Power + drives PSD10122** e PSD
10162** to reduce the emissions to the levels envisioned by EN61800-3 category C1.
The fi lter must be connected between the power supply and terminals L1/L, L2/N and earth of the drive.
Fig. 3.s
Dimensions (mm) Weight
(kg)
EMI fi lter code L1 L2 L3 B1 B2 B3 H D
PSARF10000
(CNW102.1/30)
180 150 90 98 88 70 70 5 1,3
Technical specifi cations:
Current 30A Leakage current < 3,5mA
Voltage 250V Connection by terminal 4mm
2
Temperature 60°C
Important:
Connect power supply cable and drive as shown on the label.
Position the fi lter as near as possible to the drive in a way to minimise connection cable length.
Connect the fi lter metal casing to earth.
3.13 DC Choke (PSD10**4**)
The DC choke is an optional that can be supplied separately to be used with the Power+ drives with three-phase
power supply (PSD10**4**) to reduce the harmonic currents to the levels envisioned by EN61000-3-12.
The choke has four holes for fi xing to the wall.
G
A
B
C
D
F
E
Fig. 3.t
Dimensions (mm)
Weight
(kg)
DC choke code A B C D E F G (diam)
PSACH10000, PSACH10100 86 96 98 94 84 71 5 2,7
Important:
Position the choke as near as possible to the drive in a way to minimise connection cable length (max 2m).
For connection to the drive use cables with section at least equal to the power supply cable.
Envision the space necessary for connection of the cables to the choke terminals.