41
ENG
UltraCella +0300083EN - rel. 1.5 - 07.02.2015
4.11.1 Parameters (UltraCella)
UltraCella ha un sottoinsieme di parametri dedicati alla confi gurazione
del modulo Ultra 3PH Full.
Par Description Def Min Max U.M.
cH1 3PH module serial address 1 1 247 -
cH2 3PH module off set serial address 0 0 232 -
cH3 Type of three phase module
0 = Evaporator
1 = Full
001-
cA1 Sd1 probe connection
0 = in UltraCella
1 = in 3PH module
001-
cA2 Sd2 probe connection
0 = in UltraCella
1 = in 3PH module
001-
cA3 Sc probe connection
(Full module only)
0 = in UltraCella
1 = in 3PH module
001-
cEn Enable 3PH mod.
0 = disable
1 = enable
001-
4.11.2 Function
Ultra 3PH Full Module has to be combined with UltraCella controls (P/
Ns WB000S% or WB000D%). Module has inside high power actuators
to handle directly three-phase loads of the condensing and evaporator
units, but logic and regulation algorithms are inside UltraCella.
In the table below details of where probes and loads can be connected.
Nota:
Although three-phase loads have to be physically connected to Ultra
3PH Full module, UltraCella maintains its standard confi guration of
relays.
Input
Connected
UltraCella Ultra 3PH Full module
Ambient probe
-
Defrost probe Sd1
cA1 = 0
-
cA1 = 1
-
Defrost probe auxiliary
evaporator Sd2
cA2 = 0
-
cA2 = 1
-
Condensing probe Sc
cA3 = 0
-
cA3 = 1
-
Uscita UltraCella Ultra 3PH Full module
Compressor command

(1PH)
(3PH)
Defrost heaters
(1PH)
(3PH)
Evaporator fans
(1PH)
(3PH)
Light
(1PH)
-
AUX1
(1PH)
(1PH)
AUX2
(1PH)
-
Tab. 4.g