Faults which can not be recovered manually
Display Content Cause Corrective action
oC
Over-current during stop Detection circuit malfunction Consult with the supplier
oL1
Motor overload
Loading too large
Consider increasing the
motor capacity
oL2
Inverter overload Excessive load
Consider increasing the
inverter capacity
LV-C
Voltage too low during
operation
1. Power voltage too low
2. Power voltage varies
widely (uctuates)
1. Improve power quality
2. Consider adding a
reactor at the power input
side