9 62-11646
S
TARTING
U
NIT
- C
ONTINUED
1. Place the START/RUN-OFF switch in the START/RUN position.
The unit will automatically start in the same operating state (Engine
Operation or Electric Operation) it was in when last stopped.
If required the system will initiate a “Soft Start” / “Bump Start”
procedure to clear any liquid refrigerant or oil. During this procedure,
the compressor will be started for one second and then shut down for
9 seconds, up to five times.
2. The system will display the Carrier Transicold logo, display the default
screen, present language selection and the hour meter readings (if
configured to do so) along with a test flash of the alarm light. Next the
system will perform a start sequence, energize the buzzer, and then start
the unit automatically.
If the unit attempts to start in Electric Operation, and power is not
available, the A00073 - “NO POWER - CHECK POWER CORD”
alarm will be activated. This alarm will clear if power is restored. If this
alarm condition exists for five minutes and the Functions and
Configurations are set to allow a switch, the unit will switch to Engine
Operation.
3. If there is an alarm present, the alarm message will be displayed in the
MessageCenter and the alarm LED will flash for five seconds. If one or
more shutdown alarms are present, the alarm(s) must be cleared before
the unit will start.
4. If the unit is to be switched from Engine Operation to Electric Operation or
from Electric Operation to Engine refer to Switching Operating State.
Once the unit is operating in the desired state, observe the
MessageCenter. If the word “ACTIVE” or “MODIFIED” is displayed at the
right, the unit is equipped with IntelliSet™ settings; for more information
refer to the IntelliSet™ section of this book.