21 62-11646
P
RETRIP
- C
ONTINUED
4. If START PRETRIP is selected, Pretrip will begin and the PRETRIP
STATUS screen will be displayed. Immediately following Pretrip OR if
“View Results of Last Pretrip” is selected the PRETRIP SUMMARY
SCREEN will be displayed.
At any time during Pretrip, the UNIT DATA soft key may be pressed to
allow the user to view the unit data screen, refer to Unit Data. To
return to Pretrip, press the BACK soft key.
During Pretrip the ALARM light will illuminate to indicate there is no
temperature control.
5. During Pretrip Test 1, verify that the buzzer is energized and the amber
light on the light bar is illuminated (if equipped).
6. The remainder of the Pretrip tests will run automatically and take 7 to 25
minutes. The percent of Pretrip that has been completed is displayed in
the status bar under the test description information.
7. “PRETRIP PASS”, “PRETRIP FAIL IN TEST ##” or “PRETRIP FAILED
AND COMPLETE” will be displayed at the end of the testing. The “PASS”
message will display until a key is pressed. The Pretrip test “FAIL” results
message will display until the alarms are cleared.
To end Pretrip at any time, press STOP PRETRIP soft key.
PRETRIP STATUS
PRETRIP TYPE: COOL - AMBIENT 75
o
F
TEST 2 OF 10 - CURRENT TEST
TEST STOPUNIT
RESULTS PRETRIPDATA
23%
LIV
CURRENT DRAW - 2 AMPS