81
System Heating Performance Data (Cont.)
Ducted Split System
53QDMT42-518 Heat Pump
380-420V/3Ph/50Hz
Indoor Conditions Outdoor Ambient Temperature
ESP
in.wg
Fan
Speed
Air
Flow
cfm
Temp. °C
DB
24/18°C DB/WB 7/6°C DB/WB 2/1°C DB/WB
Capacity
Btu/hr
Input
W
Capacity
Btu/hr
Input
W
Capacity
Btu/hr
Input
W
0
in.wg
High
1370
15°C
53260 3345 43020 2880 35235 2480
20°C 51620 3655 41000 3095 33185 2725
27°C 48340 3880 38510 3345 31135 2950
Medium 1260
15°C
50595 3215 40870 2770 33475 2385
20°C 49040 3510 38940 2975 31530 2620
27°C 45925 3725 36585 3215 29585 2835
Low 715
15°C
46045 2960 37190 2550 30465 2195
20°C 44630 3230 35440 2735 28695 2415
27°C 41795 3430 33295 2960 26925 2605
0.08
in.wg
High
1300
15°C
51895 3315 41915 2850 34330 2455
20°C 50295 3615 39920 3065 32335 2700
27°C 47105 3840 37525 3310 30340 2920
Medium 1190
15°C
49300 3185 39820 2740 32610 2360
20°C 47785 3475 37925 2945 30720 2590
27°C 44755 3695 35650 3180 28825 2805
Low 636
15°C
44865 2930 36235 2525 29675 2170
20°C 43480 3195 34515 2705 27955 2385
27°C 40730 3400 32445 2925 26230 2580
0.12
in.wg
High
1255
15°C
51210 3295 41360 2840 33880 2445
20°C 49635 3595 39395 3050 31905 2685
27°C 46480 3825 37030 3295 29940 2905
Medium 1145
15°C
48650 3165 39295 2725 32190 2350
20°C 47155 3455 37425 2930 30315 2575
27°C 44160 3675 35180 3165 28450 2790
Low 594
15°C
44275 2915 35760 2510 29295 2160
20°C 42915 3180 34060 2700 27585 2375
27°C 40185 3380 32010 2915 25885 2565
0.16
in.wg
High
1223
15°C
50525 3280 40810 2825 33425 2430
20°C 48975 3575 38870 3035 31485 2670
27°C 45865 3800 36535 3275 29540 2890
Medium 1113
15°C
48000 3150 38770 2710 31760 2335
20°C 46525 3435 36930 2915 29910 2560
27°C 43575 3655 34710 3145 28065 2775
Low 548
15°C
43685 2900 35285 2495 28900 2150
20°C 42340 3160 33605 2685 27225 2360
27°C 39650 3360 31590 2895 25540 2555
42QDMT42-718
38QDMT42-518