EasyManua.ls Logo

Carrier 160 Series - Start-Up, Adjustment, and Safety Check; General Start-Up Procedures

Carrier 160 Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58CV
Caution!!
For
the
following
applications,
use
the
minimum
vertical
heights
as
specified
below.
For
all
other
applications,
follow
exclusively
the
National
Fuel
Gas
Code.
FURNACE
VENT
ORIENTATION
FURNACE
INPUT
MIN.
VENT
MIN.
VERTICAL
VENT
ORIENTATION
BTUH/HR
DIAMETER
HEIGHT
( )
IN.
(mm)*
FT.
(M)**
Downflow
Vent
ee
a
then
up
454,000 132,000 110,000
5
(127)
12
(3.6)
Horizontal
Left
Vent
ea
30.
then
up
454,000
132,000
5
(127)
7
(2.1)
Horizontal
Left
ven
wo
up
154,000 132,000
5
(127)
7
(2.4)
Horizontal
Left
Vent
ee
right
454,000
5
(127)
7
(2.4)
ig.
41
Downflow
Vent
etpew
up
then
left
410,000
5
(127)
10
(8.0)
ig.
34
Downflow
Vent
ee
aT
right
410,000
5
(127)
10
(8.0)
NOTE:
All
vent
configurations
must
also
meet
National
Fuel
Gas
Code
venting
requirements
NFGC.
*4—in.
(102
mm)
inside
casing
or
vent
guard
**Including
4
in.
(102
mm)
vent
section(s)
The
horizontal
portion
of
the
venting
system
shall
slope
upwards
not
less
than
1/4-in.
per
linear
ft.
(21
mm/m)
from
the
furnace
to
the
vent
and
shall
be
rigidly
supported
every
5
ft.
(1.5
M)
or
less
with
metal
hangers
or
straps
to
ensure
there
is
no
movement
after
installation.
Sidewall
Venting
This
furnace
is
not
approved
for
direct
sidewall
horizontal
venting.
Per
section
12.4.3
of
the
NFPA
54/ANSI
Z223.1-2009,
any
listed
mechanical
venter
may
be
used,
when
approved
by
the
authority
having
jurisdiction.
Select
the
listed
mechanical
venter
to
match
the
Btuh
input
of
the
furnace
being
vented.
Follow
all
manufacturer’s
installation
requirements
for
venting
and
termination included
with
the
listed
mechanical
venter.
START-UP,
ADJUSTMENT,
AND
SAFETY
CHECK
General
FIRE
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury,
death
or
property
damage.
This
furnace
is
equipped
with
manual
reset
limit
switches
in
the
gas
control
area.
The
switches
open
and
shut
off
power
to
the
gas
valve,
if
a
flame
rollout
or
overheating
condition
occurs
in
the
gas
control
area.
DO
NOT
bypass
the
switches.
Correct
problem
before
resetting
the
switches.
1.
Maintain
115-v
wiring
and
ground.
Improper
polarity
will
result
in
rapid
flashing
LED
and
no
furnace
operation.
2.
Make
thermostat
wire
connections
at
the
24-v
terminal
block
on
the
furnace
control.
Failure
to
make
proper
con-
nections
will
result
in
improper
operation.
(See
Fig.
25
-
34.)
3.
Gas
supply
pressure
to
the
furnace
must
be
greater
than
4.5-In.
W.C,
(0.16
psig
)
but
not
exceed
14-In.
W.C.
(0.5
psig).
4,
Check
all
manual-reset
switches
for
continuity.
5.
Replace
blower
compartment
door.
Door
must
be
in
place
to
operate
furnace.
6.
Setup
switch
descriptions
The
variable
speed
furnace
con-
trol
has
DIP
switches
to
select
thermostat
staging,
blower
off
delay
timings,
air
flow
selection
and
other
operational
or
service
related
functions.
(See
Fig.
26,
53
and
Table
10.)
CUT
HAZARD
Failure
to
follow
this
caution
may
result
in
personal
injury.
Sheet metal
parts
may
have
sharp
edges
or
burrs.
Use
care
and
wear
appropriate
protective
clothing,
safety
glasses
and
gloves
when
handling
parts,
and
servicing
furnaces.
jt
REGULATOR
COVER
SCREW
PLASTIC
ADJUST
SCREW
ON/OFF
SWITCH
HIGH
STAGE
GAS
[>
PRESSURE
REGULATOR
)
ADJUSTMENT
LOW
STAGE
GAS
PRESSURE
REGULATOR
ADJUSTMENT
MANIFOLD
PRESSURE
TAP
A04167
Fig.
49
-
Redundant
Automatic
Gas
Control
Valve

Related product manuals