Machine Dehydration
Dehydration is recommended if the machine has been open for a considerable period of
time, if the machine is known to contain moisture, or if there has been a complete loss of
machine holding charge or refrigerant pressure.
Click here for Table 5A HFC-134a Pressure Temperature (F)
Click here for Figure 2817/19EX Leak Test Procedures
Click here for Table 5B HFC-134a Pressure Temperature (C)
Do not start or megohm test the compressor motor or oil pump motor, even for a
rotation check, if the machine is under dehydration vacuum. Insulation break-
down and severe damage may result.