EasyManua.ls Logo

Carrier 17/19EX - Page 188

Carrier 17/19EX
437 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
To Read Refrigerant Pressures
during pumpout or leak testing:
1.
The LID display on the machine control center is suitable for determining refrigerant-side
pressures and low (soft) vacuum. For evacuation or dehydration measurement, use a
quality vacuum indicator or manometer to ensure the desired range and accuracy. This can
be placed on the Schrader connections on each vessel (Figure 7 and Figure 8) by removing
the pressure transducer.
2.
To determine utility vessel pressure, a 30 in.-0-400 psi (-101-0-2760 kPa) gage is attached
to the vessel.
3.
Refer to Figure 32 for valve locations and numbers.
CAUTION
CAUTION
!
Transfer, addition, or removal of refrigerant in spring-isolated machines may
place severe stress on external piping if springs have not been blocked in both
up and down directions.
Click here for Figure 32Pumpout Arrangement and Valve Number Locations
(12-ft Vessel Shown)

Table of Contents

Related product manuals