Example 9 — Service3 Display Screen
To access this display from the LID default screen:
1. Press MENU.
2. Press SERVICE.
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT.
5. Scroll down to highlight SERVICE3.
Table 2, Example 9 — Service3 Display Screen
Description
Configurable
Range
Units
Reference
Point
Name
Default Value
Proportional Inc Band
Proportional Dec Band
Proportional ECW Gain
Guide Vane Travel Limit
2-10
2-10
1-3
30-100 %
gv
inc
gv
de
gv
ecw
gv
lim
6.5
6.0
2.0
50

Table of Contents