11. Connect the RED wire to the matching location on the terminal strip.
12. Connect the WHITE wire to the matching location on the terminal strip.
13. Connect the BLACK wire to the matching location on the terminal strip.
Install Field Insulation
When installing insulation at the job site, insulate the following components:
• compressor motor
• cooler shell
• cooler tube sheets
• suction piping
• motor cooling drain
• oil reclaim piping
• oil cooler refrigerant side tubing
• refrigerant liquid line to cooler
CAUTION
CAUTION
!
Protect insulation from weld heat damage and weld splatter. Cover with wet can-
vas cover during water piping installation.