19XR PIC II RAMP_DEM TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Pulldown Ramp Type:
Select: Temp=0, Load=1
0/1 1
Demand Limit + kW Ramp
Demand Limit Source
Select: Amps=0, kW=1
0/1 0
Motor Load Ramp % Min 5to20 10
Demand Limit Prop Band 3to15 % 10
Demand Limit At 20 mA 40 to 100 % 40
20 mA Demand Limit Opt 0/1 DSABLE/ENABLE DSABLE
Motor Rated Kilowatts 50 to 9999 kW 156
Demand Watts Interval 5 to 60 MIN 15
19XR PIC II TEMP_CTL TABLE CONFIGURAITON SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Control Point
ECW Control Option 0/1 DSABLE/ENABLE DSABLE
Temp Pulldown Deg/Min 2to10 ^F 3
Temperature Reset
RESET TYPE 1
Degrees Reset At 20 mA −30 to 30 ^F 10
RESET TYPE 2
Remote Temp (No Reset) −40 to 245 DEG F 85
Remote Temp (Full Reset) −40 to 245 DEG F 65
Degrees Reset −30 to 30 ^F 10
RESET TYPE 3
CHW Delta T (No Reset) 0to15 ^F 10
CHW Delta T (Full Reset) 0to15 ^F 0
Degrees Reset −30 to 30 ^F 5
Select/Enable Reset Type 0to3 0
CL-10