Table 5A Compressor Electrical Data, 30HXC Units (cont)
UNIT SIZE
30HXC
NAMEPLATE
V-Hz
(3 Phase)
COMPRESSOR NUMBERS
A1 B1
RLA LRA RLA LRA
126
208/230-60 * * * *
460-60 79.2 485 65.5 405
575-60 63.3 388 52.3 324
380-60 95.9 536 79.2 448
230-50 * * * *
346-50 * * * *
380/415-50 97.8 605 81.7 506
126-WD
208/230-60 175.4 307 144.9 256
460-60 79.2 153 65.5 128
575-60 63.3 123 52.3 102
380-60 95.9 169 79.2 141
230-50 161.7 305 134.9 255
346-50 107.3 210 89.5 176
380/415-50 97.8 191 81.7 160
136
208/230-60 * * * *
460-60 94.9 580 65.5 405
575-60 75.8 484 52.3 324
380-60 114.9 641 79.2 448
230-50 * * * *
346-50 * * * *
380/415-50 118.8 715 81.7 506
136-WD
208/230-60 210.0 367 144.9 256
460-60 94.6 183 65.5 128
575-60 75.8 147 52.3 102
380-60 114.9 203 79.2 141
230-50 196.3 361 134.9 255
346-50 130.3 248 89.5 176
380/415-50 118.8 226 81.7 160
146
208/230-60 * * * *
460-60 94.9 580 79.2 485
575-60 75.8 484 63.3 388
380-60 114.9 641 95.9 536
230-50 * * * *
346-50 * * * *
380/415-50 118.8 715 97.8 605
146-WD
208/230-60 210.0 367 175.4 307
460-60 94.9 183 79.2 153
575-60 75.8 147 63.3 123
380-60 114.9 203 95.9 169
230-50 196.3 361 161.7 305
346-50 130.3 248 107.3 210
380/415-50 118.8 226 97.8 191
161
208/230-60 * * * *
460-60 103.1 685 71.2 525
575-60 82.4 548 56.9 420
380-60 124.8 757 86.2 580
230-50 * * * *
346-50 * * * *
380/415-50 128.6 856 88.2 600
161-WD
208/230-60 228.8 433 157.6 350
460-60 103.1 216 71.2 175
575-60 82.4 173 56.9 140
380-60 124.8 239 86.2 193
230-50 212.5 432 145.7 348
346-50 141.0 297 96.7 232
380/415-50 128.6 270 88.2 200
171
208/230-60 * * * *
460-60 86.1 580 103.1 685
575-60 68.8 484 82.4 548
380-60 104.2 641 124.8 757
230-50 * * * *
346-50 * * * *
380/415-50 105.8 715 128.6 856
171-WD
208/230-60 190.6 367 228.8 433
460-60 86.1 183 103.1 216
575-60 68.8 147 82.4 173
380-60 104.2 203 124.8 239
230-50 174.8 361 212.5 432
346-50 116.0 248 141.0 297
380/415-50 105.8 233 128.6 270
LEGEND
LRA Locked Rotor Amps
RLA Rated Load Amps
WD Wye-Delta Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.