22
Fan data
30RY Minimum available Nominal available Maximum available
static pressure* static pressure static pressure
Pressure Flow Pressure Flow Pressure Flow
Pa l/s Pa l/s Pa l/s
017-026 0 2500 100 1940 150 1530
033 0 2920 100 2500 200 1940
040-050 0 4580 150 3890 230 3330
060 0 5560 150 4720 230 4030
070-080 0 6810 150 5830 230 5280
* Operation without duct system
Maximum air entering temperature, °C
30RY At minimum At nominal At maximum
air flow air flow air flow
017-026 44 46 47.5
033 44 46 47
040-050 44.5 46 47
060 44.5 46 47
070-080 44.5 46 47
Performance correction factors
30RY Cooling capacity Power input
Min. flow Max. flow* Min. flow Max. flow*
017-026 0.98 1.01 1.03 0.97
033 0.98 1.005 1.03 0.98
040-050 0.985 1.005 1.02 0.98
060 0.985 1.005 1.02 0.98
070-080 0.985 1.005 1.01 0.98
* Operation without duct system
Correction factor for the published performances, given at nominal air flow
Accessory suction filter pressure drop
Unit size
Additional pressure drop, Pa
0
2
4
6
8
10
12
14
017/026 033 040/050 060 070/080
Accessory reference number:
30RY-017-033: 30RY-900—002—EE—
30RY-040-080: 30RY-900—012—EE—
Replacement filter reference number:
—KH—12AE-005—EE—
30RY-017-033: quantity: 4
30RY-040-080: quantity: 6
The connection of the return air duct is now very easy, directly
on the air filter accessory.
Filter access for maintenance is ensured by removing the two
Metric screws on the unit side (rear view of the unit).
The cover panel, supplied with a handle, can now be removed.
The filters are attached to each other with a bracket that permits
sliding them into the frames.
10.5.3 - Fan discharge
A square flange is supplied mounted on the unit. An available
standard round flange can easily be installed at the fan discharge,
if the installer prefers the use of a round connection duct.
The unit is supplied with a cover panel on the discharge
side. This panel has to be removed before connection to the
duct system.
30RY-017-033: standard 560 mm diameter fan
30RY-040-080: standard 710 mm diameter fan
It is advisable to make the connection to the duct system with a
flexible collar. If this recommendation is not observed, a lot of
vibration and noise may be transmitted to the building structure.
The unit construction does not permit the support of a duct
weighing more than 10 kg. Non-observance may lead to
damage of the unit.
10.5.4 - Applicable regulations for units used with an air
duct system
Ensure that the return or supply air openings cannot accidentally
be obstructed by panels (for example low return air or opening
of doors).
Unit performances are given for an air-side pressure drop that
is indicated in the Physical Data table.
The three tables that follow contain fan characteristics, maxi-
mum air entering temperatures and performance correction
factors, depending on the air system used with the units.