19
No. Status Unit
Displayed text* Description
26 no/yes - High Pres Override Cir A High pressure override, circuit A
27 no/yes - High Pres Override Cir B High pressure override, circuit B
28 no/yes - High Pres Override Cir C High pressure override, circuit C
* Depends on the selected language (English by default).
RECLAIM – Reclaim
No. Status Unit
Displayed text* Description
1 0 to 1 - Heat Reclaim Select Heat reclaim selection
2 - °C Reclaim Entering Fluid Reclaim entering water temperature
3 - °C Reclaim Leaving Fluid Reclaim leaving water temperature
4 0 to 100 % Reclaim Valve Position Reclaim valve position
5 - - Reclaim Status Circuit A Reclaim status, circuit A
6 - kPa Pumpdown Pressure Cir A Pump-down pressure, circuit A
7 - °C Sub Condenser Temp Cir A Subcooling condenser temperature, circuit A
8 - °C Pumpdown Saturated Tmp A Pump-down saturated temperature, circuit A
9 - ^C Subcooling Temperature A Subcooling temperature, circuit A
10 o/on - Air Cond Entering Valv A Air condenser entering valve status, circuit A
11 o/on - Water Cond Enter Valve A Water condenser entering valve status, circuit A
12 o/on - Air Cond Leaving Valve A Air condenser leaving valve status, circuit A
13 o/on - Water Cond Leaving Val A Water condenser leaving valve status, circuit A
14 - - Reclaim Status Circuit B Reclaim status, circuit B
15 - kPa Pumpdown Pressure Cir B Pump-down pressure, circuit B
16 - °C Sub Condenser Temp Cir B Subcooling condenser temperature, circuit B
17 - °C Pumpdown Saturated Tmp B Pump-down saturated temperature, circuit B
18 - ^C Subcooling Temperature B Subcooling temperature, circuit B
19 o/on - Air Cond Entering Valv B Air condenser entering valve status, circuit B
20 o/on - Water Cond Enter Valve B Water condenser entering valve status, circuit B
21 o/on - Air Cond Leaving Valve B Air condenser leaving valve status, circuit B
22 o/on - Water Cond Leaving Val B Water condenser leaving valve status, circuit B
*Depends on the selected language (English by default).
FREECOOL – Free cooling
No. Status Unit Displayed text* Description
1 - - GENERAL PARAMETERS GENERAL PARAMETERS
2 0 to 1 - Free Cooling Disable? Free cooling mode status
3 - ^C LWT-OAT Delta LWT – OAT Delta
4 - - CIRCUIT A Circuit A
5 - kW Mechanical Cooling Power Mechanical cooling power
6 - kW Free Cooling Maxi Power Free cooling maximum power
7 - min Next session allowed in Next session allowed after the specied time
8 - min Cooling/FreeCool Timeout Cooling/free cooling timeout
9 no/yes - Free Cool Conditions OK? Optimal free cooling conditions
10 no/yes - Free Cool Request ? Free cooling request
11 o/on - Free Cooling Heaters ? Free cooling heaters status
12 no/yes - Free Cooling Active Free cooling status
13 - - Fan Staging Number Fan stage
14 o/on - Discharge valve Open out Discharge valve open output
15 o/on - Dischrge valve Close out Discharge valve close output
16 - - Discharge valve status Discharge valve status
17 o/on - Bypass valve Open out Bypass valve open output
18 o/on - Bypass valve Close out Bypass valve close output
19 - - Bypass valve status Bypass valve status
20 o/on - Refrigerant Pump Out Refrigerant pump output
21 - kPa Pump Inlet Pressure Pump inlet pressure
22 - kPa Pump Outlet Pressure Pump outlet pressure
23 - kPa Pump Dierential Press. Pump dierential pressure
24 0 to 100 % EXV position EXV position
25 - °C Free cooling Liquid Tmp Free cooling liquid temperature
26 - ^C Free cooling Subcool Tmp
Free cooling subcooling temperature
27 - ^C Free cooling Subcool Spt Free cooling subcooling setpoint
28 - - CIRCUIT B Circuit B
29 - kW Mechanical Cooling Power Mechanical cooling power
30 - kW Free Cooling Maxi Power Free cooling maximum power
31 - min Next session allowed in Next session allowed after the specied time
32 - min Cooling/FreeCool Timeout Cooling/free cooling timeout
33 no/yes - Free Cool Conditions OK? Optimal free cooling conditions
34 no/yes - Free Cool Request ? Free cooling request
35 o/on - Free Cooling Heaters ? Free cooling heaters status
36 no/yes - Free Cooling Active Free cooling status