14
Climatic Curves
Parameters 112 and 117 set to 0 (see table 1) allows to load
in the control a custom climatic curve.
Below gures show which parameter of installer
conguration table need to be set to create customized
heating and cooling curves.
0
5
10
15
20
15 20 25 30 35 40 45
par 4
1
2
3
4
15
25
35
45
55
65
-15 -10 -5 0 5 10 15 20 25
par 4
1
2
3
4
Outside Temperature
HEATING CLIMATIC CURVE
COOLING CLIMATIC CURVE
Outside Temperature
Water TemperatureWater Temperature
1. (Parameter No 121)
2. (Parameter No 120)
3. (Parameter No 118)
4. (Parameter No 119)
1. (Parameter No 125)
2. (Parameter No 124)
3. (Parameter No 123)
4. (Parameter No 122)
Climatic Custom Curves
NOTE:
When NUI is installed (par 100 set to 3) or SUI Comfort mode is installed (par 100 set to 2), control is expecting the choice
between a custom or pre-set climatic curve. In case application requires xed water set point in necessary to set an
horizontal climatic curve by setting par.120=121 for Heating Climatic Curve and 124=125 for Cooling Climatic Curve.