Factory Conguration Mode (Table 2)
FEATURE
PARAMETER
NUMBER
DESCRIPTION
VALUE
RANGE
DEFAULT
VALUE
INSTALLER
VALUE
Min Max
UNIT
CONFIGURATION
302
0. Cooling Only
02 11. Heat & Cooling
2. Heating Only
Clock
Operational and connection information
Press zone ( ) and mode (M) buttons at a time for 10
seconds to enter into the factory conguration mode.
When this setting is rst selected, 799 shall be displayed
in the temperature-zone and an initial value of 10 shall be
displayed in the time-zone of the display. Press and hold
the down button. When the counter reaches zero, “Fd” shall
be displayed in the temperature-zone of the display. This
represents factory defaults are in progress. Upon successful
completion of restoring defaults to EEPROM, the NUI shall
then force a reset.
The clock will continue to operate for 8 hours while power
is removed.
Room Air Temperature Sensor Failure:
If the sensor used to sense room air temperature reads
less than -45°C or greater than 65°C, it shall be considered
failed. If it has been agged as failed, the room temperature
displays will show “--”.
Humidity Sensor Failure:
If the sensor used to sense room Humidity reads less than
0 HR% or greater than 99 HR%, it shall be considered failed.
If it has been agged as failed, the Humidity displays will
show “--”.
EEPROM Failure:
If the thermostat non-volatile memory (EEPROM) has failed,
an “E4” error shall be shown in the room air temperature
display. When this error is present and power is cycled to
the thermostat all of the installer congurations, program
schedule settings and user settings will be factory default
values. This may result in incorrect equipment operation.
There is no eld x for this error. The thermostat must be
replaced.
Communication Failure
If the NUI does not receive CCN communications from the
main user interface for 60 seconds, the display will show
“E3” error code in the Temperature display area and ‘-‘in all
the Time Display Area. Under this condition the outside
temperature will be blanked.
“E3” error code will be displayed once and the other
functionality will remain same. If this happens then check
the communication cable between NUI and outdoor unit.