14
PERFORMANCE DATA (CONT.)
COOLING CAPACITIES
COOLING ONLY 38HDF030 WITH 40KMC03036
Tem p ° F (° C)
Air Entering
Condenser
(Edb)
Air Entering Evaporator --- Cfm/BF
635 / 0.05 720 / 0.05 875 / 0.05
Air Entering Evaporator --- Ewb ° F (° C)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
55
(12.8)
TCG 27.3 29.8 32.6 35.0 28.8 30.9 33.8 36.0 30.6 32.6 35.4 37.0
SHG 25.9 23.7 20.7 17.4 27.8 25.3 21.9 18.1 30.6 27.9 24.3 19.0
TC 26.8 29.4 32.1 34.5 28.1 30.3 33.2 35.4 29.8 31.8 34.7 36.2
kW 1.56 1.57 1.58 1.59 1.57 1.57 1.59 1.59 1.57 1.59 1.58 1.61
CMP 1.28 1.29 1.30 1.31 1.25 1.26 1.27 1.28 1.21 1.23 1.22 1.25
LDB 43.3 46.8 51.5 56.6 45.4 48.9 53.5 58.6 48.7 51.8 55.8 61.6
LWB 39.4 44.7 50.0 55.8 41.0 46.4 51.8 57.6 43.3 48.9 54.2 60.2
65
(18.3)
TCG 26.3 28.8 31.7 34.6 27.4 29.9 32.8 35.6 29.7 31.4 34.0 36.8
SHG 25.4 23.3 20.3 17.2 27.4 24.9 21.6 18.1 29.7 28.2 23.0 19.2
TC 25.8 28.3 31.2 34.1 26.8 29.3 32.2 35.0 29.0 30.7 33.2 36.1
kW 1.73 1.75 1.77 1.78 1.74 1.76 1.76 1.78 1.76 1.75 1.78 1.78
CMP 1.45 1.47 1.49 1.50 1.42 1.44 1.45 1.46 1.40 1.40 1.43 1.43
LDB 44.1 47.4 52.0 56.8 45.9 49.3 53.8 58.6 49.7 51.5 57.1 61.4
LWB 40.3 45.4 50.5 56.0 41.8 47.1 52.3 57.7 43.7 49.4 54.8 60.2
75
(23.9)
TCG 25.5 27.6 30.5 33.4 26.6 28.6 31.6 34.5 28.8 30.0 32.7 35.7
SHG 24.5 22.8 20.0 16.8 26.6 24.4 21.1 17.7 28.8 26.5 22.6 18.9
TC 25.0 27.1 30.0 32.9 26.0 28.0 31.0 33.9 28.0 29.2 32.0 35.0
kW 1.92 1.94 1.96 1.98 1.93 1.95 1.97 1.98 1.96 1.97 1.98 1.99
CMP 1.64 1.66 1.68 1.70 1.62 1.64 1.65 1.66 1.60 1.61 1.63 1.63
LDB 45.4 48.1 52.4 57.4 47.0 49.9 54.5 59.2 50.7 53.2 57.6 61.8
LWB 40.8 46.2 51.3 56.6 42.4 47.8 52.9 58.3 44.2 50.1 55.3 60.6
85
(29.4)
TCG 24.2 26.4 29.2 32.0 25.6 27.3 30.3 33.1 27.7 28.8 31.5 34.3
SHG 24.2 22.2 19.5 16.0 25.6 24.0 20.5 17.1 27.7 26.3 22.4 18.4
TC 23.7 25.9 28.7 31.5 25.0 26.7 29.6 32.5 27.0 28.0 30.8 33.6
kW 2.13 2.15 2.18 2.20 2.15 2.17 2.19 2.20 2.17 2.18 2.19 2.21
CMP 1.85 1.87 1.90 1.92 1.83 1.85 1.87 1.88 1.82 1.83 1.84 1.85
LDB 45.8 49.0 53.2 58.5 48.2 50.5 55.2 59.8 51.8 53.4 57.7 62.2
LWB 41.8 47.0 52.1 57.4 43.0 48.5 53.6 58.9 44.8 50.6 55.8 61.1
95
(35.0)
TCG 23.2 24.9 27.7 30.7 24.5 25.9 28.7 31.6 26.6 27.2 29.8 32.8
SHG 23.2 21.7 18.6 15.7 24.5 23.3 19.9 16.6 26.6 25.6 21.7 17.8
TC 22.7 24.4 27.2 30.2 23.9 25.3 28.1 31.0 25.8 26.5 29.0 32.0
kW 2.36 2.38 2.43 2.43 2.38 2.40 2.42 2.44 2.41 2.42 2.52 2.54
CMP 2.08 2.10 2.15 2.15 2.06 2.08 2.11 2.12 2.05 2.07 2.17 2.19
LDB 47.2 49.6 54.3 59.0 49.6 51.4 55.9 60.5 53.0 54.1 58.3 62.8
LWB 42.5 48.0 53.0 58.1 43.7 49.4 54.4 59.6 45.3 51.3 56.4 61.7
105
(40.6)
TCG 22.0 23.4 26.2 29.1 23.3 24.3 27.1 29.8 25.3 25.9 28.3 31.0
SHG 22.0 21.0 18.1 15.1 23.3 22.4 19.6 15.6 25.3 24.5 21.2 17.1
TC 21.6 22.9 25.7 28.6 22.7 23.7 26.5 29.2 24.5 25.1 27.6 30.2
kW 2.60 2.62 2.68 2.69 2.62 2.64 2.68 2.69 2.66 2.67 2.68 2.70
CMP 2.32 2.34 2.40 2.41 2.31 2.32 2.37 2.38 2.31 2.32 2.33 2.35
LDB 48.9 50.6 55.1 59.7 51.1 52.4 56.3 61.6 54.3 55.3 58.9 63.6
LWB 43.4 49.0 53.9 58.9 44.4 50.2 55.2 60.4 46.0 51.9 57.1 62.3
115
(46.1)
TCG 20.8 21.7 24.4 27.3 22.0 22.5 25.2 28.0 23.8 24.1 26.3 29.0
SHG 20.8 20.1 17.4 14.5 22.0 21.5 18.8 15.0 23.8 23.5 20.4 16.5
TC 20.3 21.2 23.9 26.9 21.4 21.9 24.6 27.4 23.1 23.3 25.5 28.3
kW 2.87 2.88 2.94 2.96 2.89 2.90 2.96 2.96 2.93 2.94 2.96 2.97
CMP 2.59 2.60 2.66 2.68 2.58 2.58 2.64 2.65 2.58 2.58 2.60 2.62
LDB 50.7 51.9 56.0 60.6 52.8 53.5 57.3 62.4 55.8 56.4 59.7 64.1
LWB 44.2 50.1 54.9 59.9 45.2 51.2 56.1 61.2 46.7 52.7 57.9 63.0
125
(51.7)
TCG 19.4 19.8 22.4 25.3 20.6 20.8 23.2 26.0 22.3 22.3 24.2 26.8
SHG 19.4 19.1 16.7 13.7 20.6 20.2 17.8 14.4 22.3 22.3 19.7 15.7
TC 18.9 19.4 21.9 24.8 19.9 20.1 22.6 25.4 21.5 21.5 23.5 26.1
kW 3.15 3.15 3.23 3.24 3.18 3.18 3.24 3.25 3.22 3.22 3.24 3.26
CMP 2.87 2.87 2.95 2.96 2.86 2.86 2.92 2.93 2.87 2.87 2.88 2.90
LDB 52.7 53.3 57.1 61.7 54.6 55.2 58.5 63.1 57.4 57.6 60.5 64.9
LWB 45.2 51.2 56.0 60.9 46.1 52.2 57.1 62.1 47.5 53.4 58.7 63.8
Rating condition
Not recommended for long---term operation.
LEGEND
BF --- Bypass Factor
CMP --- Compressor
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
k W --- To ta l Po we r
LDB --- Leaving Dry Bulb
L W B --- L e a v i n g W e t B u l b
SHG --- Gross Sensible Ca pacity (1000 Btu/hour)
TC --- Total Net Cool ing Capacity (1000 Btu/hour)
---
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. Th e SHG is based on 80_F (26.67_C) edb temperature of air
entering indoor coil.
Below 80_F (26.67_C) edb, subtract (corr factor x cfm) from
SHG.
Above 80_F (26.67_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).