EasyManua.ls Logo

Carrier 38HDF - Outside Air and Air Discharge; Air Throw Data; Sound Ratings

Carrier 38HDF
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
Outside Air -- Up to 20% outside air can be introduced to the
40KMC or 40KMQ through pre--punched knockouts.
If the 40KMC or 40KMQ is installed close to an outside wall,
some outside air can be introduced by running field supplied
ductwork to the unit. the amount of outside air that can be
introduced is determined by using the chart in Fig. 9.
If the cassette is installed in the middle of a room and is not close to
an outside wall, a power ventilation kit can be used to overcome
the static pressure in the ductwork and allow the needed CFM.
For applications that are very sound sensitive, it is recommended to
limit the fresh air intake to 10% when using a power ventilation
kit.
Air Discharge -- The 40KMC and 40KMQ units have four
discharge outlets that are equipped with motorized louvers for
better comfort. The user has three operating choices with the
louvers
1. AUTO -- The position of the louver is determined by the
mode in which the unit is running.
2. CONTINUOUS -- Louvers move continuously
3. STATIONARY -- Louver position is determined by the
user.
Air can be discharged from 4, 3, or 2 louvers. An accessory kit is
required to block the discharge from each louver.
Air Throw Data -- The following table shows the air throw data of
the 40KMC and 40KMQ units. The numbers shown indicate the
maximum distances reached by the airflow with a speed equal to or
greater than .66 ft/sec (0.2 m/sec) with louvers in the cooling
position.
AIR THROW DATA*
Model
4LouversOpen
ft (m)
3LouversOpen
ft (m)
2LouversOpen
ft (m)
4 0 K M C 0 1 8 --- --- --- 3 15.75 (4 .8) 17.4 (5.3) 19.0 (5.8)
4 0 K M C 0 2 4 --- --- --- 3 9.8 (3.0) 11.5 (3.5) 13.0 (4.0)
40KMC03036 --- --- --- 3 14.1 (4.3) 15.75 (4.8) 17.4 (5.3)
40KMQ01824 --- --- --- 3 9.8 (3.0) 11.5 (3.5) 13.0 (4.0)
40KMQ03036 --- --- --- 3 14.1 (4.3) 15.75 (4.8) 17.4 (5.3)
* High Speed
SOUND RATINGS
Outdoor Units
Model Number Sound Power dBA Sound Pressure dBA
3 8 H D F 0 1 8 --- --- --- 3 66 55
3 8 H D F 0 2 4 --- --- --- 3 66 55
3 8 H D F 0 3 0 --- --- --- 3 72 61
38HDF036--- --- --- 3/5/6 72 61
3 8 Q R F 0 1 8 --- --- --- 3 66 55
3 8 Q R F 0 2 4 --- --- --- 3 66 55
3 8 Q R F 0 3 0 --- --- --- 3 72 61
38QRF036--- --- --- 3/5/6 72 61
Indoor Units
Model Number
High Medium Low
Sound Power
dBA
Sound Pressure
dBA
Sound Power
dBA
Sound Pressure
dBA
Sound Power
dBA
Sound Pressure
dBA
4 0 K M C 0 1 8 --- --- --- 3 55 44 51 40 48 37
4 0 K M C 0 2 4 --- --- --- 3 49 38 45 34 42 31
40KMC03036 --- --- --- 3 58 47 55 44 50 39
40KMQ01824 --- --- --- 3 49 38 45 34 42 31
40KMQ03036 --- --- --- 3 58 47 55 44 50 39
NOTES: Te s t e d i n a c c o r d a n c e w i th A RI S ta n da r d 2 7 0 --- --- --- 9 5 a n d A R I 3 5 0 ( n o l is te d i n A R I) .
4QKMC, KMQ / 38HDF, QRF