PERFORMANCE DATA (CONT.)
COOLING CAPACITIES
HEAT / COOL 38HDF036 WITH 40KMQ03036
Tem p ° F (° C)
Air Entering
Condenser
(Edb)
Air Entering Evaporator --- Cfm/BF
635 / 0.05 720 / 0.05 875 / 0.05
Air Entering Evaporator --- Ewb ° F (° C)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
55
(12.8)
TCG 34.7 37.8 41.1 43.9 36.3 39.4 42.6 45.2 38.5 41.5 44.5 46.5
SHG 32.0 28.5 25.1 21.7 34.5 30.6 26.3 22.7 37.6 33.3 28.4 23.7
TC 34.3 37.3 40.6 43.4 35.7 38.8 42.0 44.6 37.8 40.8 43.8 45.8
kW 2.08 2.11 2.12 2.12 2.09 2.11 2.13 2.12 2.10 2.12 2.14 2.11
CMP 1.65 1.68 1.70 1.69 1.63 1.65 1.67 1.66 1.60 1.62 1.64 1.61
LDB 34.6 40.0 45.3 50.5 36.8 42.2 48.0 53.0 41.4 46.3 51.7 56.9
LWB 33.5 38.8 44.4 50.5 35.8 41.2 46.8 53.0 39.0 44.5 50.2 56.5
65
(18.3)
TCG 33.5 36.9 40.3 43.4 35.1 38.3 41.7 44.8 37.8 40.3 43.6 46.1
SHG 31.3 28.1 24.8 21.1 33.6 29.8 26.0 22.1 37.2 32.7 28.1 23.2
TC 33.0 36.4 39.8 42.9 34.4 37.7 41.1 44.2 37.0 39.6 42.9 45.4
kW 2.31 2.33 2.34 2.37 2.32 2.34 2.36 2.37 2.33 2.35 2.36 2.38
CMP 1.88 1.91 1.92 1.94 1.86 1.88 1.90 1.91 1.83 1.85 1.86 1.88
LDB 35.5 40.5 45.7 51.3 38.0 43.2 48.4 53.8 41.8 46.9 52.0 57.5
LWB 34.6 39.5 44.9 50.8 36.7 41.9 47.3 53.2 39.4 45.1 50.6 56.6
75
(23.9)
TCG 32.3 35.5 39.1 42.3 33.7 36.9 40.4 43.7 36.7 38.9 42.3 45.2
SHG 30.6 27.5 24.2 20.7 32.8 29.2 25.5 21.6 35.2 32.2 27.6 22.8
TC 31.8 35.0 38.6 41.8 33.1 36.3 39.8 43.1 35.9 38.2 41.6 44.5
kW 2.55 2.59 2.60 2.62 2.57 2.60 2.61 2.63 2.59 2.60 2.62 2.64
CMP 2.13 2.16 2.18 2.20 2.11 2.14 2.15 2.17 2.09 2.10 2.12 2.14
LDB 36.6 41.5 46.5 52.0 39.0 44.0 49.0 54.3 43.9 47.4 52.5 57.8
LWB 35.5 40.5 45.7 51.5 37.6 42.8 48.1 53.8 40.0 45.8 51.2 57.0
85
(29.4)
TCG 30.8 34.1 37.6 41.0 32.4 35.5 39.0 42.3 34.9 37.4 40.8 43.7
SHG 29.8 26.8 23.4 20.1 31.9 28.6 24.8 21.0 34.9 31.6 27.0 22.2
TC 30.3 33.6 37.1 40.5 31.8 34.9 38.3 41.7 34.2 36.7 40.1 42.9
kW 2.82 2.86 2.89 2.90 2.84 2.88 2.89 2.91 2.88 2.88 2.90 2.92
CMP 2.39 2.44 2.46 2.48 2.38 2.42 2.43 2.45 2.38 2.38 2.40 2.42
LDB 37.7 42.4 47.6 52.8 40.2 44.7 49.9 55.1 44.2 48.0 53.1 58.4
LWB 36.7 41.6 46.8 52.3 38.5 43.7 48.9 54.5 41.0 46.5 51.9 57.6
95
(35.0)
TCG 29.3 32.5 36.0 39.5 31.1 33.8 37.3 40.7 33.5 35.8 36.8 42.1
SHG 28.9 26.0 22.7 19.4 30.6 27.8 24.1 20.3 33.5 30.9 24.7 21.6
TC 28.8 32.0 35.5 39.0 30.5 33.2 36.7 40.1 32.8 35.0 36.0 41.3
kW 3.11 3.15 3.19 3.21 3.13 3.18 3.20 3.22 3.18 3.19 3.27 3.28
CMP 2.68 2.73 2.77 2.79 2.67 2.72 2.74 2.76 2.68 2.69 2.77 2.78
LDB 39.0 43.6 48.6 53.7 41.9 45.7 50.8 55.9 45.6 48.7 53.8 59.0
LWB 37.9 42.8 47.8 53.2 39.4 44.7 49.8 55.3 41.7 47.3 52.6 58.2
105
(40.6)
TCG 27.7 30.6 34.0 37.8 29.4 31.9 35.5 38.9 32.0 33.7 37.1 40.3
SHG 27.7 25.0 21.7 18.7 29.4 26.9 23.3 19.6 32.0 30.0 25.4 20.9
TC 27.2 30.1 33.5 37.3 28.8 31.3 34.9 38.3 31.2 33.0 36.4 39.5
kW 3.42 3.47 3.53 3.55 3.45 3.50 3.54 3.56 3.51 3.53 3.55 3.58
CMP 3.00 3.04 3.11 3.13 2.99 3.04 3.08 3.10 3.01 3.03 3.05 3.08
LDB 40.8 44.9 50.0 54.8 43.3 46.8 51.7 56.8 47.3 49.6 54.7 59.7
LWB 39.1 44.1 49.1 54.2 40.5 45.9 50.8 56.2 42.6 48.3 53.5 58.9
115
(46.1)
TCG 26.2 28.5 32.2 35.8 27.8 29.7 33.3 36.8 30.2 31.5 35.0 38.1
SHG 26.2 24.0 21.1 17.9 27.8 25.9 22.4 18.8 30.2 29.0 24.7 20.1
TC 25.7 28.0 31.7 35.3 27.2 29.1 32.7 36.2 29.5 30.7 34.2 37.4
kW 3.77 3.81 3.90 3.92 3.80 3.84 3.90 3.93 3.86 3.89 3.91 3.94
CMP 3.34 3.38 3.47 3.49 3.34 3.38 3.44 3.47 3.36 3.39 3.41 3.44
LDB 42.9 46.3 50.9 55.8 45.4 48.1 52.9 57.8 49.1 50.6 55.5 60.5
LWB 40.3 45.6 50.3 55.3 41.6 47.1 52.0 57.2 43.5 49.4 54.4 59.7
125
(51.7)
TCG 24.5 26.2 29.8 33.4 26.0 27.4 30.9 34.4 28.3 30.0 32.5 35.6
SHG 24.5 22.9 20.1 17.0 26.0 24.8 21.3 17.9 28.3 26.9 23.7 19.1
TC 24.0 25.7 29.3 32.9 25.4 26.8 30.3 33.7 27.6 29.2 31.7 34.8
kW 4.14 4.18 4.28 4.30 4.17 4.21 4.29 4.31 4.25 4.25 4.30 4.33
CMP 3.72 3.75 3.86 3.88 3.71 3.75 3.83 3.85 3.75 3.75 3.80 3.83
LDB 45.4 47.8 52.3 57.1 47.6 49.4 54.2 58.9 51.1 52.8 56.4 61.5
LWB 41.6 47.1 51.7 56.6 42.7 48.5 53.3 58.3 44.4 50.1 55.4 60.7
Rating condition
LEGEND
BF --- Bypass Factor
CMP --- Compressor
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
k W --- To ta l Po we r
LDB --- Leaving Dry Bulb
L W B --- L e a v i n g W e t B u l b
SHG --- Gross Sensible Ca pacity (1000 Btu/hour)
TC --- Total Net Cool ing Capacity (1000 Btu/hour )
TCG --- Gross C ooling C a pacity (1000 Btu/hour)
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. Th e SHG is based on 80_F (26.67_C) edb temperature of air
entering indoor coil.
Below 80_F (26.67_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.67_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).