38MBRC: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
14
Enquiry Information
Table 7 — Enquiry Information
ENQUIRY INFORMATION DISPLAY VALUE MEANING REMARK
T1,T2,T3,T4, T2B,TP,TH,
Targeted Frequency,
Actual Frequency
- 1F,- 1E,- 1d,- 1c,- 1b,- 1A - 25,- 24,- 23,- 22,- 21,- 20
1. All the displaying temperature is actual
value.
2. Temperature is
C no matter the remote.
3. T1,T2,T3,T4,T2B display range:- 25 ~ 70,
4. TP display range:- 20 ~ 130.
5. Frequency display range: 0 ~ 159HZ.
6. If the range, it displays the
maximum value or minimum
value.
- 19—99 - 19—99
A0,A1,
A9 100,101,109
b0,b1,
b9 110,111,119
c0,c1,
c9 120,121,129
d0,d1,
d9 130,131,139
E0,E1,
E9 140,141,149
F0,F1,
F9 150,151,159
Indoor fan speed/
Outdoor fan speed
0OFF
1,2,3,4
Low speed, Medium speed,
High speed, Turbo
For some big capacity motors
14- FF
Actual fan speed = Display value turns to
decimal value and then multiply 10. The unit is
RPM.
For some small capacity motors the display
value is 14 - FF (hexadecimal), the
corresponding fan speed range is from 200-
2550 RPM.
EXV opening angle 0- FF
Actual EXV opening value = Display value
turns to decimal value and then multiply 2.
Compressor continuous
running time
0- FF 0- 255 minutes
If the actual value exceeds the range, it
displays the maximum value or minimum
value.
Compressor stop causes 0- 99
For a detailed meaning, consult with an engi-
neer
Decimal display
Reserve 0- FF