38MBRC: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
32
PC 30 (High Pressure Protection Diagnosis and Solution)
Description: Outdoor pressure switch cuts off the system when high pressure is higher than 4.4 MPa
Recommended parts to prepare:
• Connection wires
•Pressure switch
• Outdoor fan
• Outdoor main PCB
Troubleshooting and repair:
 Are the high pressure switch 
and main control board wired 
correctly?
 
Method:  Disconnect the plug. 
Measure the resistance of the 
high pressure protector ,  if the 
protector is normal the value is 
o,  Does a problem still exist ?
Yes
Yes
No
No
 Is  the high pressure 
protector broken?
Is the outdoor ambient 
temperature is higher than 
50ć?
No
Yes
Check if the outdoor unit 
ventilation is good
Yes
Is the heat exchanger dirty ?
No
Yes
 Replace outdoor main board .  Is 
the problem resolved?
No
High pressure protection 
Is the outdoor fan running 
properly?
No
Yes
NO
Connect high pressure switch and 
main control board
Replace high pressure protector
Stop the unit 
Ensure that  the outdoor unit 