Installation Place
• A place which provides the spaces around the outdoor unit as
shown in the diagram
• A place which can bear the weight of the outdoor unit and does
not allow an increase in noise level and vibration
• A place where the operation noise and discharged air do not
disturb your neighbors
• A place which is not exposed to a strong wind
• A place free of a leakage of combustible gases
• A place which does not block a passage
• When the outdoor unit is to be installed in an elevated position,
be sure to secure its feet.
• An allowable length of the connecting pipe is up to 10 m for
38VYX025-R and 15 m for 38VYX035-R.
• An allowable height level is up to 8 m for 38VYX025-R and 10 m for
38VYX035-R
• A place where the drain water does not raise any problems
CAUTION
1.Install the outdoor unit without anything blocking the air
discharging.
2.When the outdoor unit is installed in a place always exposed
to strong wind like a coast or on a high storey of a building,
secure the normal fan operation using a duct or a windshield.
3.In particularly windy areas, install the unit such as to avoid
admission of wind.
4.Installation in the following places may result in trouble.
Do not install the unit in such places.
• A place full of machine oil
• A saline-place such as the coast
• A place full of sulfide gas
• A place where high-frequency waves are likely to be
generated as from audio equipment, welders, and medical
equipment
Strong
         wind
GB - 2
ero
mrommB
eromromm
A
Saddle
Vinyl tape
Apply after carrying
out a drainage test.
600 m
m
o
mr
oer
Extension
drain hose
(Not available,
provided by
installer)
er
om
r
o
mmA
m
001
m
mroer
o
eromromm006
B
m
mo
mr
oer
Extension drain hose
(Not available, provided
by installer)
e
r
o
mr
om
m006
6
00 m
m
o
mro
er
38VYX025-R  38VYX035-R
m
0
01m
mroe
ro
Remark :
• Detail of accessory and installation
parts can see in the accessory sheet.
38VYX025-R
38VYX035-R
A 400 mm 600 mm
B 45 mm 100 mm
Optional Installation
Parts
Parts name
Refrigerant piping
Liquid side : ∅6.35 mm
Gas side : ∅9.52 mm 
Pipe insulating material
(polyethylene foam, 6 mm thick)
Putty, PVC tapes
Q’ty
One
each
1
One
each
(38VYX025-R, 38VYX035-R)
Fixing bolt arrangement of outdoor unit
600 mm
90 mm
125 mm
115 mm
32,5 mm
mm37
mm201
m
m
01
3
mm7
3
0
500 mm
97 mm
mm06
m
m
5
72
• Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be
exposed to a strong wind.
• Use ∅8 mm or ∅10 mm anchor bolts and nuts.
• If it is necessary to drain the defrost water, attach drain nipple  and cap
water proof   to the bottom plate of the outdoor unit before installing it.
Drain outlet
Air outlet
Air inlet
38VYX025-R
Air outlet
Air inlet
Drain outlet
38VYX035-R
9