COMBINATION RATINGS*
OUTDOOR
UNIT
S I Z E ---
SERIES
INDOOR UNIT
NOMINAL
A I R --- F L O W
Cooling Capacity @ 95˚F(35˚C) Heating Capacity
Rated
BTUH
Capacity
kW
Power
kW
Rated
EER
H i g h --- Te m p @ 4 7 ˚F(8˚C) L o w --- Te m p @ 1 7 ˚F ( --- 8 ˚C)
CFM L/S
Rated
BTUH
Capacity
kW
Power
kW
Rated
BTUH
Capacity
kW
Power
kW
018---7A
FB4BSF018
FB4BSF024
600
600
280
280
17000
17600
4.9
5.16
2.00
1.96
8.50
9.00
17400
17800
5.10
5.22
1.76
1.74
9000
9200
2.64
2.70
1.39
1.42
024---7A
FB4BSF024
FB4BSF030
800
800
380
380
23000
23600
6.74
6.91
2.56
2.62
9.00
9.00
23000
23600
6.74
6.91
2.41
2.47
14000
14400
4.10
4.22
1.71
1.76
036---7A, 9A
FB4BSF036
FB4BS(F,B)042
1200
1200
550
550
35000
35500
10.25
10.40
3.89
3.94
9.00
9.00
36000
37000
10.55
10.84
3.40
3.50
22100
22100
6.48
6.48
2.65
2.65
048---7A, 9A
FB4BS(F,B)048
FB4BS(F,B)060
1600
1600
750
750
46500
47000
13.62
13.77
5.17
5.22
9.00
9.00
47000
47000
13.77
13.77
4.28
4.28
28000
28000
8.20
8.20
3.71
3.71
060---9A
FB4BS(F,B)060
FB4BSF070
1850
1850
850
850
57000
58000
16.70
16.99
6.33
6.44
9.00
9.00
59000
59000
17.29
17.29
5.21
5.21
39000
39000
11.43
11.43
4.45
4.45
* Ratings are net valu es r eflecting the eff ects of circulating fan heat. Su pplemental electric heat is n ot included.
Ratings are based on:
Cooling Standard: 80_F(27_C) db 67_F(19_C) wb indoor entering air temperature and 95_F(35_C) db air entering outdoor unit.
High---Temp Heating Standard: 70_F(21_C) db indoor entering air temperature and 47_F(8_C) db 43˚F(6_C) wb air entering outdoor unit.
Low--- Temp Heating Standard: 70_F(21_C) db indoor entering air temperature and 17_F(±9_C) db 15˚F(±10_C) wb air entering outdoor unit.
SEER — Seasonal Energy Efficiency Ratio
COP — Coefficient of Performance
TDR — T i m e --- D e l a y R e l ay
HSPF — Heating Seasonal Performance Factor
EER — Energy Efficiency Ratio