GUIDE SPECIFICATIONS
GENERAL
AIR--COOLED, SPLIT --SYSTEM HEAT PUMP
38YCC
1--1/2 TO 5 NOMINAL TONS (7 TO 17.5 kW)
System Description
Outdoor--mounted, air--cooled, split--system heat pump unit
suitable for ground or rooftop installation. Unit consists of a
hermetic compressor, an air--cooled coil, propeller-- type condenser
fan, and a control box. Unit will discharge supply air upward as
shown on contract drawings. Unit will be used in a refrigeration
circuit to match up to a packaged fan coil or coil unit.
Quality Assurance
— Unit shall be manufactured in a facility registered to
ISO9001/BS5750 Part II, International Standard for
Quality Systems.
— Unit construction will comply with latest edition of
ANSI/ASHRAE and with NEC (U.S.A. Standard).
— Unit cabinet will be capable of withstanding Federal Test
Method Standard No. 141 (Method 6061) 500--hr salt
spray test (U.S.A. Standard).
— Air-- cooled condenser coils will be leak tested at 150
psig (1034 KPa) and pressure tested at 300 psig (2068
KPa).
Delivery, Storage, and Handling
— Unit will be shipped as single package only and is stored
and handled per unit manufacturer’s recommendations.
PRODUCTS
Equipment
— Factory--assembled, single--piece, air--cooled heat pump
unit. Contained within the unit enclosure is all factory
wiring, piping, controls, compressor, refrigerant charge
(R22), and special features required prior to field
start--up.
Unit
Cabinet
— Unit cabinet will be constructed of galvanized,
prepainted steel.
Fans
— Condenser fan will be direct--drive propeller type,
discharging air upward.
— Condenser fan motors will be totally enclosed, 1--phase
type with class B insulation and permanently lubricated
bearings. Shafts will be corrosion resistant.
— Fan blades will be statically and dynamically balanced.
— Condenser fan openings will be equipped with coated
steel wire safety guards.
Compressor
— Compressor will be hermetically sealed.
— Compressor will be mounted on rubber vibration
isolators.
Condenser
Coil
— Condenser coil will be air cooled.
— Coil will be constructed of epoxy coated, enhanced
aluminum fins mechanically bonded to copper tubes
which are then cleaned, dehydrated, and sealed.
Refrigeration
Components
— Refrigeration circuit components will include liquid line
shutoff valve with sweat connections, vapor shutoff
valves with sweat connections, system charge of R--22
refrigerant, compressor oil, accumulator, and reversing
valve.
Operating Characteristics
— The capacity of the unit will meet or exceed _____ Btuh
(_____ kW) at a suction temperature of _____ _F
(______C). The power consumption at full load will not
exceed _____ kW.
— Combination of the unit and the evaporator or fan coil
unit will have a total net cooling capacity of _____ Btuh
(_____ kW) or greater at conditions of _____ CFM
(_____ L/S) entering air temperature at the evaporator at
_____ _F (______C) wet bulb and _____ _F
(______C) dry bulb, and air entering the unit at ____ _F
(______C).
— The system will have a SEER of _____ Btuh/watt or
greater at DOE conditions.
Electrical Requirements
— Nominal unit electrical characteristics will be _____ v,
_____ phase, 50 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v to
_____ v.
— Nominal unit electrical characteristics will be _____ v,
three phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v to
_____ v.
— Unit electrical power will be single point connection.
— Control circuit will be 24v.
Special Features
— Refer to section of this literature identifying accessories
and descriptions for specific features and available
enhancements.