DETAILED COOLING CAPACI TIES* (ENGLISH) CONTINUED
COIL AIR CONDENSER ENTERING AIR TEMPERATURES ˚ C
L/S
(C)
EWB
75 85 95 105 115 125
Capacity MBtuh†
Sys.
Power
kW**
Capacity MBtuh†
Sys.
Power
kW**
Capacity MBtuh†
Sys.
Power
kW**
Capacity MBtuh†
Sys.
Power
kW**
Capacity MBtuh†
Sys.
Power
kW**
Capacity MBtuh†
Sys.
Power
kW**
To t a l Sens‡ To t a l Sens‡ To t al Sens To t a l Sens‡ To t a l Sens‡ To t a l Sens‡
38YCC060--9A Outdoor Section With FB4BSF060 Indoor Section
1750
72
67
62
57
67.5
61.9
56.8
55.2
33.7
43.0
52.0
55.2
5.11
4.91
4.74
4.69
64.7
59.3
54.5
53.3
32.7
41.9
50.9
53.3
5.61
5.41
5.24
5.20
61.8
56.5
52.0
51.3
31.6
40.8
49.6
51.3
6.18
5.97
5.79
5.76
58.6
53.7
49.5
49.1
30.5
39.7
48.3
49.1
6.81
6.59
6.41
6.39
55.5
50.8
47.0
46.9
29.4
38.6
46.8
46.9
7.51
7.27
7.09
7.09
52.0
47.6
44.4
44.4
28.2
37.3
44.4
44.4
8.27
8.02
7.84
7.84
1900
72
67
62
57
68.1
62.5
57.6
56.4
34.6
44.6
54.2
56.4
5.19
4.99
4.83
4.79
65.2
59.8
55.2
54.5
33.6
43.5
53.0
54.5
5.70
5.49
5.32
5.30
62.1
57.0
52.8
52.3
32.5
42.4
51.7
52.3
6.26
6.05
5.88
5.87
59.0
54.1
50.2
50.1
31.4
41.3
50.1
50.1
6.89
6.67
6.50
6.50
55.8
51.2
47.9
47.8
30.3
40.1
47.9
47.8
7.59
7.36
7.19
7.20
52.3
47.9
45.2
45.3
29.1
38.9
45.2
45.3
8.36
8.11
7.96
7.96
2000
72
67
62
57
68.6
62.8
58.0
57.2
35.2
45.7
55.6
57.2
5.24
5.04
4.88
4.86
65.6
60.1
55.6
55.1
34.2
44.6
54.3
55.1
5.75
5.54
5.38
5.36
62.6
57.3
53.1
53.0
33.1
43.5
52.8
53.0
6.32
6.10
5.93
5.93
59.3
54.4
50.8
50.7
32.0
42.4
50.8
50.7
6.95
6.72
6.56
6.57
56.0
51.3
48.4
48.4
30.9
41.1
48.4
48.4
7.65
7.41
7.26
7.26
52.5
48.0
45.7
45.7
29.7
39.9
45.7
45.7
8.41
8.16
8.03
8.03
2150
72
67
62
57
69.0
63.3
58.7
58.2
36.1
47.2
57.5
58.2
5.32
5.12
4.96
4.95
66.0
60.5
56.2
56.1
35.1
46.1
55.9
56.1
5.83
5.62
5.46
5.46
62.9
57.7
53.9
53.9
34.0
45.0
53.9
53.9
6.39
6.18
6.03
6.03
59.6
54.7
51.6
51.5
32.9
43.9
51.6
51.5
7.03
6.80
6.66
6.66
56.2
51.6
49.1
49.1
31.8
42.7
49.1
49.1
7.73
7.49
7.36
7.36
52.7
48.3
46.5
46.5
30.6
41.4
46.5
46.5
8.49
8.24
8.13
8.13
Cooling Indoor Model Capacity Power
FB4BSF060 1.00 1.00
FB4BSF070 1.02 1.02
NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* D etailed cooling capacities are based on indoor a nd outdoor u nit at the same eleva tion per ARI standard 210/240 ---94. If additional tubing length a n d/or indoor unit is located above outdoor unit, a slight variation in capacity may
occur.
{ Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
} Sensible capacities shown are based on 80˚F(27˚C) entering air at the indoor coil. For sensible capacities at other than 80˚F(27˚C), deduct 835 Btuh ( 245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below
80˚F(27˚C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80˚F(27˚C).
** Unit kW is total of indoor and outdoor unit kilowatts.
EWB --- Entering Wet Bulb