20
HEAT PUMP HEATING PERFORMANCE (S.I.) (CONT.)
INDOOR AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES ˚C
--- 1 6 --- 8 0 4 8 12 16 20
(C)
EDB
L/S
Capacity kW
Tota l
Power
kW*
Capacity kW
Tota l
Power
kW*
Capacity kW
Tota l
Power
kW*
Capacity kW
Tota l
Power
kW*
Capacity kW
Tota l
Power
kW*
Capacity kW
Tota l
Power
kW*
Capacity kW
Tota l
Power
kW*
Capacity kW
Tota l
Power
kW*
Tota l Integ† Tota l Integ† Tot a l Integ† Tot a l Integ† Total Integ† Total Integ† To t a l Integ† Total Integ†
38YCC060---9A Outdoor Section With FS4BSF060 Indoor Section
12
850
900
950
1000
9.46
9.50
9.54
9.59
8.70
8.73
8.77
8.81
3.51
3.53
3.55
3.57
11.7
11.7
11.7
11.8
10.6
10.7
10.7
10.7
3.72
3.73
3.74
3.76
14.3
14.3
14.4
14.4
12.8
12.9
12.9
13.0
4.00
4.00
4.01
4.02
15.7
15.8
15.9
15.9
14.7
14.7
14.8
14.9
4.17
4.17
4.18
4.19
17.4
17.4
17.5
17.6
17.3
17.3
17.4
17.5
4.37
4.36
4.37
4.38
19.4
19.4
19.5
19.6
19.4
19.4
19.5
19.6
4.65
4.64
4.64
4.65
21.6
21.8
21.7
21.7
21.6
21.8
21.7
21.7
4.98
4.97
4.96
4.97
24.0
24.3
24.0
24.0
24.0
24.3
24.0
24.0
5.34
5.33
5.32
5.32
15
850
900
950
1000
9.42
9.46
9.51
9.55
8.66
8.70
8.74
8.78
3.73
3.75
3.77
3.79
11.6
11.7
11.7
11.7
10.6
10.6
10.6
10.7
3.96
3.97
3.98
4.00
14.2
14.3
14.3
14.4
12.8
12.8
12.9
12.9
4.25
4.25
4.26
4.27
15.7
15.7
15.8
15.9
14.6
14.7
14.7
14.8
4.43
4.43
4.43
4.44
17.3
17.3
17.4
17.5
17.2
17.3
17.3
17.4
4.64
4.63
4.64
4.64
19.2
19.3
19.4
19.4
19.2
19.3
19.4
19.4
4.93
4.91
4.91
4.91
21.4
21.5
21.5
21.6
21.4
21.5
21.5
21.6
5.26
5.24
5.23
5.23
23.7
23.9
23.7
23.8
23.7
23.9
23.7
23.8
5.63
5.61
5.60
5.60
18
850
900
950
1000
9.38
9.43
9.47
9.51
8.63
8.67
8.70
8.74
3.95
3.97
3.99
4.01
11.6
11.6
11.6
11.7
10.5
10.6
10.6
10.6
4.20
4.20
4.21
4.23
14.1
14.2
14.2
14.3
12.7
12.8
12.8
12.9
4.51
4.50
4.51
4.52
15.6
15.6
15.7
15.8
14.5
14.6
14.6
14.7
4.69
4.69
4.69
4.69
17.2
17.3
17.3
17.4
17.1
17.2
17.2
17.3
4.91
4.90
4.90
4.90
19.1
19.2
19.2
19.3
19.1
19.2
19.2
19.3
5.20
5.18
5.18
5.18
21.2
21.3
21.3
21.4
21.2
21.3
21.3
21.4
5.54
5.52
5.51
5.50
23.4
23.6
23.5
23.6
23.4
23.6
23.5
23.6
5.91
5.89
5.88
5.87
21
850
900
950
1000
9.34
9.39
9.43
9.47
8.59
8.63
8.67
8.71
4.17
4.19
4.21
4.23
11.5
11.6
11.6
11.6
10.5
10.5
10.6
10.6
4.44
4.44
4.45
4.46
14.1
14.1
14.2
14.2
12.7
12.7
12.8
12.8
4.76
4.76
4.76
4.77
15.5
15.6
15.6
15.7
14.4
14.5
14.6
14.6
4.96
4.95
4.94
4.95
17.1
17.2
17.2
17.3
17.0
17.1
17.2
17.2
5.19
5.17
5.16
5.16
18.9
19.0
19.1
19.2
18.9
19.0
19.1
19.2
5.48
5.46
5.45
5.44
21.0
21.0
21.1
21.2
21.0
21.0
21.1
21.2
5.82
5.79
5.78
5.77
23.1
23.2
23.3
23.4
23.1
23.2
23.3
23.4
6.20
6.17
6.15
6.14
24
850
900
950
1000
9.29
9.34
9.38
9.43
8.54
8.59
8.62
8.67
4.40
4.42
4.43
4.45
11.5
11.5
11.6
11.6
10.5
10.5
10.5
10.6
4.69
4.69
4.70
4.71
14.0
14.1
14.1
14.2
12.6
12.6
12.7
12.7
5.03
5.02
5.02
5.02
15.4
15.5
15.5
15.6
14.4
14.4
14.5
14.5
5.23
5.21
5.21
5.21
16.9
17.0
17.1
17.1
16.9
16.9
17.0
17.1
5.46
5.44
5.43
5.43
18.8
18.9
18.9
19.0
18.8
18.9
18.9
19.0
5.77
5.74
5.72
5.72
20.8
20.9
21.0
21.0
20.8
20.9
21.0
21.0
6.12
6.09
6.07
6.06
22.9
23.0
23.1
23.2
22.9
23.0
23.1
23.2
6.52
6.48
6.45
6.44
Cooling Indoor Model Capacity Power
FB4BSF060 1.00 1.00
FB4BSF070 0.99 0.95
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation i s not an acceptable practice.
* The kW values include the compressor, outdoor fan motor, and indoor blower motor. The kw from supplement heaters should be added to these values to obtain total system kilowatts.
{ The kW heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The kW heating from supplement heaters should be added to those values to obtain total system capacity.
EDB --- E n t e r i ng D r y B u l b
38YCC