Technical specifications
Power supply operating voltage 15-35VDC
power dissipation Typical current output 10mA +
Connection wiring terminal max1.5 mm
2
(AWG 16)
Sensing element sensor
scope
E+E Dual-source infrared system
0…2000ppm
accuracy @25ć, 1013mbar <±(50ppm+2%
*
mv)
Signal output signal output 4…20mA
Environment temperature
humidity
-20…60°C
<95% RH. non-condensing
temperature
humidity
-20…60°C
<95% R.H. non-condensing
Dimension diagram mm (inch)
Installation
The product is composed of two parts: (a) probe and (b) upper shell. It shall be installed at position with
smooth air circulation. Position with 2-3 meters distance from fan or cooling coil is recommended to
achieve accurate measurement.
1. Drill diameter 13mm hole on duct and use four tapping screws to fix the shell tightly on duct
2. Open the shell
3. Connecting signals in line with electrical diagrams.
4. Insert the probe in, use two tapping screws to fix the shell tightly on duct
5. Install the shell
6. Fix the screws
7. Screw driver #2, suggest using AMC-2 for cable protection