3
 Introduction of Control components 
1. Control board: SE-serial single digital controller 
 
 
 
 
 
 
 
 
SE6166 
SE-serial controllers provide a complete solution for single unit control application.It can be widely 
used in common environments including roof, machine room, control panel and other special places. It can 
fully support EIKON®-LogicBuilder, and be flexible to support BACnet protocol communication based 
on ARCNET 156 Kbps or BACnet MS/TP. 
Main features
¾ Support BACnet protocol communication based on ARCNET 156 Kbps or BACnet MS/TP 
¾ Control accuracy increase due to 12bit A/D resolution for all inputs, some inputs support a pluse 
of 40Hz 
¾ High speed microprocessors with 1 mbyte flash memory for control program storage, supporting 
for upgrade through remote network  
¾ Real-time clock function for power loss protection, which enables unit independent operation even 
in case of network interruption 
¾ Removable terminal for easy installation and maintenance  
¾ Support graphic oriented programming and also provide peer-to-peer communication with other 
ME-serial or ZN-serial controller 
 
Technical specifications  
BACnet Port 
Comply with BACnet Advanced Application Controller (B-AAC) defined by 
appendix L of 135-2004δBACnetε, ANSI-ASHRAE Standard 
Local access port 
EIA-485 supports BACnet access of ARCNET 156 Kbps or BACnet MS/TP (9600 
baud to 76.8 Kbps).Rnet port is used for job-site local access  
Digital output  24VAC 3A relay, manual-shut off-auto switch, with LED indicator  
Inputs 
0-5 VDC, 0-10 VDC, 0-20 mA, thermistor (10k Ohm typeĊ), 1k Ohm RTD 
(Platinum, nickel, Balco), dry contact 
Input resolution   12 bit A/D 
Impulse input  Input point 1 and point 2 support for 40 Hz (minimum impluse width as 12.5ms) 
Analog output  0-10VDC, 0-20mA, with LED indicator 
Output reolution  8 bit D/A 
Microprocessor   High-speed 16 bit microprocessor with ARCNET communication coprocessor 
Memory  
1MB flash memory, 1MB power-loss protection memory, 16 bit memory bus (service 
life of battery is 10 years ,which offers 10,000 hours power-loss protection )