23
2. Malfunction of Blocked Protection of IDU Fan Motor H6
End
No
Yes
No
Yes
Yes
Yes
Yes
No
No
No
Yes
Yes
No
Turn the fan blades
 
by hand under
 
power-off condition
Do the fan blades rotate 
smoothly with little to no 
resistance  
Adjust the motor and blade 
assembly so the rotor can run 
smoothly.
Under power-off condition, 
check whether the wiring terminal 
between
 indoor fan and main 
board is loose.
Turn unit on 
to check whether the 
malfunction is 
eliminated.
Turn unit on 
to check whether the 
malfunction is 
eliminated.
Reinsert the wiring 
terminal of indoor fan.
It's the malfunction of main board.
Replace a new main board that is 
of the same model.
It's the malfunction of main board.
Replace a new main board that is 
of the same model.
Replace a new board of the same 
model.
It's the malfunction of main board.
Then check whether the voltage 
between terminal 2 and terminal 3 
of the motor interface is 15VDC.
Connect power and restart the unit. 
Test whether the voltage between terminal 1 and terminal 2 
of motor interface is within 280~310VDC.
Then check whether there is voltage 
between terminal 2 and terminal 4 
of the motor interface.
It's the malfunction of motor. 
Replace a new motor that is 
of the same model.
Start
No
Fig. 26 – Troubleshooting