EasyManua.ls Logo

Carrier 40GRQB12B-3 - Phase Current of Compressor Is over Current; IPM Protection, De- Synchronizing Malfunction

Carrier 40GRQB12B-3
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36
3. IPM protection, de- synchronizing malfunction, phase current of compressor is over current (AP1 below is control board of outdoor unit)
Main detection points:
S Is the control board AP1 and compr essor COMP wel l
connec t ed or are they loos e? Is the conne ction sequence
correct?
S Is the voltage i nput in the norma l range (test the volt age
betwe en L1, L2 of the wiring board XT wit h a DC volt age
meter)?
S Is the compressor coil resistance normal? Is the
compressor coil insulated to the copper pipe well?
S Is the coil blocked with dirt and debris?
S Isthechargecorrect?
Malfunction diagnosis process:
Energize and
switch on
IPM protection
occurs after the
machine has run for
a
p
eriod of time?
Use AC voltmeter
to measure the
voltage between
terminal L and N
on the wiring
board XT)
If the voltage
between terminal L
and N on wiring
board XT is within
210VAC~250VAC?
Check the supply
voltage and
restore it to
210VAC~250VAC
Voltage between
the two ends of celectrolytic
capacitor (test3) is
Restart the unit. Before
protection occurs,
use DC voltmeter to
measure the voltage
between the two
ends of electrolytic
capacitor on control
panel AP1
(test3)
Does the unit
operate
normally?
Please confirm:
1. If the indoor and
outdoor heat
exchangers are
dirty?
2. Are the indoor
and outdoor fans
working normally?
3. If the environment
temperature is too
high, resulting in
the system
pressure exceeding
the high pressure
threshold.
4. Is the unit
overcharged?
5. Other conditions
resulting in the
system pressure
being too high.
The connection
of capacitor C2
is loose.
Reconnect the
capacitor C2 according
to Electrical Wiring
Diagram. Then,
Restart the
unit.
Stop the unit and
disconnect the power
supply. Wait 20 minutes,
or use DC voltmeter to
measure the voltage
between the two ends of
capacitor C2, until the
voltage is lower than 20V
Replace the capacitor
C2. Then, energize
and start the unit.
Replace the
control panel AP1
Take corrective actions
according to Technical
Service Manual, and
then energize and start
the unit.
If there is any
abnormality
described above?
Replace the
control panel AP1
If the connection
between AP1 and
COMP is unsecure
or the connection
order is wrong?
Connect the control panel
A
P1 and compressor
COMP correctly according
to the Electrical Wiring
Diagram. Then, energize
and start the unit.
Use ohmmeter to
measure the resistance
between the three
terminals on compressor
COMP, and compare the
measurements with the
compressor resistance on
Service Manual.
If the
resistance is
normal?
Use ohmmeter to
measure the resistance
between the two
terminals of compressor
COMP and copper tube.
Replace the
compressor
COMP
Resistance higher
than 500MΩ?
Replace the
control panel
AP1
END
Y N
Y
N
Y
Y
Does the unit
operate
Y
Y
N
N
Y
N
If the unit can
work normally?
Y
N
N
normally?
Y
Y
N
N
N
Y
higher than
250V
Remove the wires
on the two ends of
capacitor C2. Then,
use capacitance
meter to measure
the capacitor C2.
Verify as per the
Parameters Sheet.
Stop the unit and
disconnect the power
supply. Then, check
the connection of
capacitor C2
according to Electrical
Wiring Diagram.
If capacitor
C2 is failed?
Refer to the
Electrical Wiring
Diagram and check
if the connection
between AP1 and
COMP is loose and if
the connection order
is correct.
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Y
Yes
normally?
Does the unit
operate
normally?
Does the unit
operate
Fig. 39 Troubleshooting

Table of Contents

Related product manuals