36
3. IPM protection, de- synchronizing malfunction, phase current of compressor is over current (AP1 below is control board of outdoor unit)
Main detection points:
S Is the control board AP1 and compr essor COMP wel l
connec t ed or are they loos e? Is the conne ction sequence
correct?
S Is the voltage i nput in the norma l range (test the volt age
betwe en L1, L2 of the wiring board XT wit h a DC volt age
meter)?
S Is the compressor coil resistance normal? Is the
compressor coil insulated to the copper pipe well?
S Is the coil blocked with dirt and debris?
S Isthechargecorrect?
Malfunction diagnosis process:
Energize and 
switch on
IPM protection 
occurs after the 
machine has run for 
a
eriod of time?
Use AC voltmeter 
to measure the 
voltage between 
terminal L and N 
on the wiring 
board XT)
If the voltage 
between terminal L 
and N on wiring 
board XT is within 
210VAC~250VAC?
Check the supply 
voltage and 
restore it to 
210VAC~250VAC
Voltage between 
the two ends of celectrolytic 
capacitor (test3) is 
Restart the unit. Before 
protection occurs, 
use DC voltmeter to 
measure the voltage 
between the two 
ends of electrolytic 
capacitor on control 
panel AP1 
(test3)
Does the unit  
operate
normally? 
Please confirm:   
1. If the indoor and 
outdoor heat 
exchangers are 
dirty?  
2. Are the indoor  
 
 
 
and outdoor fans 
working normally? 
3. If the environment 
temperature is too 
high, resulting in 
the system 
pressure exceeding 
the high pressure 
threshold.
4. Is the unit 
overcharged?
 
 
 
5. Other conditions 
resulting in the 
system pressure 
being too high.
The connection 
of capacitor C2 
is loose.
Reconnect the 
capacitor C2 according 
to Electrical Wiring 
Diagram. Then, 
Restart the
unit.
Stop the unit and 
disconnect the power 
supply. Wait 20 minutes, 
or use DC voltmeter to 
measure the voltage 
between the two ends of 
capacitor C2, until the 
voltage is lower than 20V
Replace the capacitor 
C2. Then, energize 
and start the unit.
Replace the 
control panel AP1
Take corrective actions 
according to Technical 
Service Manual, and 
then energize and start 
the unit.
If there is any 
abnormality 
described above?
Replace the 
control panel AP1
If the connection 
between AP1 and 
COMP is unsecure 
or the connection 
order is wrong?
Connect the control panel 
P1 and compressor 
COMP correctly according 
to the Electrical Wiring 
Diagram. Then, energize 
and start the unit.
Use ohmmeter to 
measure the resistance 
between the three 
terminals on compressor 
COMP, and compare the 
measurements with the 
compressor resistance on 
Service Manual.
If the 
resistance is 
normal?
Use ohmmeter to 
measure the resistance 
between the two 
terminals of compressor 
COMP and copper tube.
Replace the 
compressor 
COMP
Resistance higher 
than 500MΩ?
Replace the 
control panel 
AP1
END
Y N
Y
N
Y
Does the unit  
     operate 
Y
Y
N
Y
N
If the unit can 
work normally? 
Y
N
N
normally?
Y
Y
N
N
N
Y
higher than 
      250V
  Remove  the  wires
  on the two ends of
capacitor C2. Then,
use capacitance
meter to measure
the capacitor C2.
Verify as per the
Parameters Sheet.
    Stop the unit and
  disconnect the power
  supply. Then, check
  the connection of
capacitor C2
according to Electrical
Wiring Diagram.
If capacitor
C2 is failed?
    Refer to the
    Electrical Wiring
   Diagram and check
   if the connection
between AP1 and
COMP is loose and if
the connection order
is correct.
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Y
Yes
normally? 
Does the unit  
     operate 
normally? 
Does the unit  
     operate 
Fig. 39 – Troubleshooting