3. High temperature and overload protection (E8) (AP1 below means control board of outdoor unit)
Main detection points:
S Is the outdoor ambient temperature in normal range?
S Is the indoor and outdoor fan running normally?
S Is the condensing unit blocked with dirt and debris?
 
E8 is displayed
              If the outdoor 
ambient temperature is higher
              than 127°F? 
Normal protection, unit starts
when ambient temperature 
lowers.
Unit restarts 
   normally
Unit restarts 
   normally
Is the unit clear of debris
and the coil is clean?
 
     Clean the heat exchanger 
and remove surrounding obstacles
Are the indoor and outdoor 
fan running normally?
Are the connections
            tight?
Adjust the 
connection
Replace outdoor 
mainboard
Replace mainboard
Replace Motor
Replace Fan 
   capacitor
Fan capacitor is broken?
Motor is broken?
End
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Fig. 32 – Troubleshooting