4. Diagnosis for anti- high temperature, overload protection (AP1 below is control board of the outdoor unit).
Main detection points:
S If the outdoor ambient temperature is in the normal range
S If the indoor and outdoor fan is running normal
S Are the units clear of dirt and debris?
Malfunction diagnosis process:
1. Check if fan terminal 
OFAN is connected well
2. Test if resistance value 
of any two terminals is less 
than 1k
 with ohmic meter
Do the indoor and outdoor 
fan work?
After the unit
de-energized for 20min
Replace
control board
AP1
Outdoor unit coils clean? 
Clean coils
Replace 
outdoor fan
Y
Replace fan 
capacitor C1
     High temperature,
overload protection
Above operating envelope 
If the outdoor ambient temperature is 
higher than 127 ºF?
No
No
Y
No
End
Yes
Yes
Yes
Fig. 40 – Troubleshooting