OUTDOOR UNIT REMOVAL PROCEDURE
UNIT DAMAGE HAZARD
Be sure to wait for a minimum of 20 minutes after turning
off all power supplies and discharge the refrigerant
completely before removal.
WARNING
!
09K/12K
top cover
3. Remove panel and grille
2. Remove cable cross plate sub-assy and valve cover
1. Remove top cover
cable cross
plate sub-assy
valve cover
panel
grille
Remove the screws connecting top cover, left and
right side plate, as well as panel, to remove the top
cover.
Remove the screws fixing panel, to remove the panel.
Remove the screws connecting panel grille and panel,
loosen the clamp, to remove the panel grille.
Remove the screws connecting
cable cross plate
sub-assy
and right side plate, to remove the
cable
cross plate sub-assy
. Remove the screw fixing
valve cover, to remove the cover.