ELECTRICAL DATA
38HDF/38QRF
UNIT SIZE
018
O24
36QRF030
36HDF030
035
036
V-PH-Hz
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
Table 10 - 38HDF/38QRF Electrical Data
VOLTAGERANGE* COMPRESSOR OUTDOOR FAN MOTOR
Min Max
187 253
187 253
187 253
187 253
187 253
187 253
414 506
187 253
187 253
414 506
RLA
9.0
12.8
14.1
14.1
16.7
10.4
5.8
17.9
13.2
6.0
LRA
48.0
58.3
73.0
73.0
79.0
73.0
38.0
112.0
88.0
44.0
FLA
0.80
0.80
1.50
0.80
1.50
1.50
0.80
1.45
1.45
0.80
NEC Hp
0.125
0.125
0.25
0.125
0.25
0.25
0.25
0.25
0.25
0.25
kW Out
0.09
0.09
0.19
0.09
0.19
0.19
0.19
0.19
0.19
0.19
MIN CKT
AMPS
12.1
16.8
18.4
18.4
22.3
14.5
8.7
23.8
18.0
8.3
FUSE/
CKT
BKR
AMPS
2O
25
3O
3O
35
2O
15
4O
3O
15
40KMC
Unit Size
018
024
030
036
V-PH-Hz
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
Table 11 - 40KMC Fan coil Electrical Data
Voltage Range FAN
Min. Max
187 253
187 253
187 253
187 253
FLA Wafts
0.55 120
0.50 110
0.95 210
0.95 210
Condensate
Pump FLA
0.06
0.06
0.06
0.06
Louver
Motor
FLA
0.01
0.01
0.01
0.01
Power
MIN CKT
AMPS
0.8
0.7
1.3
1.3
FUSE/
CKT
BKR
AMPS
15
15
15
15
40KMQ
Unit Size
018
024
030
036
V-PH-Hz
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
Table 12 - 40KMQ Fan Coil Electrical Data
Voltage
Range
Min. Max
187 253
187 253
187 253
187 253
FAN
Motor
FLA Power
(Wa_s)
0.50 110
0.50 110
0.95 210
0.95 210
*Permissible limits of the voltage range at which unit will operate satisfactorily.
LEGEND
FLA - Full Load Amps
MCA - Minimum Circuit Amps per NEC Section 430-24
NEC - National Electrical Code
RLA - Rated Load Amps (Compressor)
Louver
Condensate
Motor
Pump FLA
FLA
0.06 0.01
0.06 0.01
0.06 0.01
0.06 0.01
Electric
Heaters
MIN
kW FLA CKT
AMPS
3 12.5 16.3
3 12.5 16.3
3 12.5 16.9
3 12.5 16.9
Power
FUSE/
CKT
BKR
AMPS
2O
2O
2O
2O
NOTES:
1. In compliance with NEC requirements for multi-motor and combination
load equipment (refer to NEC Articles 430 and 440), the over-current
protective device for the unit shall be fuse or equipped with a breaker.
2. Motor RLA values are established in accordance with UL (Underwriters
Laboratories) Standard 465.
@s
11