No. Item Outline of specifications Remarks
13
Self-clean
operation
(Dry operation):
1) When cooling operation mode (AUTO COOL, COOL, DRY) stopped, the
following three self-clean operations are performed.
Compressor
ON period
Self-clean
operation period
FAN Drain pump Louver
0 to 10 min. None
Fan (UL) STOP Horizontal discharge position10 to 60 min. 1 hour
60 min. to 2 hours
2) During operation of self-clean, lights on the wired
remote controller screen. However the operation lamp
(Green LED) goes off.
3) To stop the self-clean operation, push twice the
[ON/OFF] button on the remote controller continuously.
(Stop the operation as compressor ON time in the
table above: 10 minutes or below.)
4) When the follower unit executes self-clean operation in
the group connection, the segment of
is displayed
on the wired remote controller screen via master unit.
* If self-clean operation is not used, set invalidity
(does not use) of the self-clean operation by
changing [0001 (At shipment) of Item code (DN) [D3]
to [0000].
*
To erase the
display during operation of self-
clean, change Item code [D4] from [0000: Display
(At shipment)] to [0001: Non-display].
Not possible to set
by wireless remote
controller.
It is recognized as
[STOP] from the
remote monitor side.
14
Save operation
1) Turn on
button on the remote controller.
2) During operation of save operation,
lights on the
wired remote controller.
3) During save operation, the current release control is
performed with the restriction ratio set in EEPROM on
the outdoor unit.
4) The restriction ratio can be set by keeping
button pushed for 4 seconds or more on the remote
controller.
5) When validating the save operation, the next operation
starts with save operation valid because contents
are held even when operation stops, operation mode
changes or power supply is reset.
6) The restriction ratio can be set by changing the setup
data of Item code (DN) [C2] in the range of 50 to 100%
(every 1%, Setting at shipment: 75%).
Not possible to set
by wireless remote
controller.
Carry out setting
operation during stop
of the unit; otherwise
the unit stops
operation.
For the setup
operation, refer to
“How to set up contents
of save operation” of
Installation Manual.