[E04 error]
Does outdoor operate?
Is group address setup of
remote controller correct?
Are wiring in indoor unit and
1, 2, 3 inter-unit cables correct?
Are wirings of terminal blocks
(1, 2, 3) wired to CN67 normal?
Does the voltage between 2 and 3
of terminal blocks (1, 2, 3) vary?
Check indoor P.C. board.
Defect Replace
Check outdoor P.C. board.
Defect Replace
Check indoor P.C. board.
Defect Replace
Correct wiring of connector
and terminal blocks.
Correct wiring and
inter-unit cables.
Check CODE No. [14].
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
(MCC-1643)
As shown in the following figure,
carry out measurement within 20 seconds
after the power was turned on.
Black
S5277G
White
Terminal block
3
2
1
SVM-13050.indb 48SVM-13050.indb 48 6/27/13 10:35 AM6/27/13 10:35 AM
- 58 -