Procedure 5
Push check button to cancel (release from) the test
run mode.
([TEST] disappears on the display and the status
returns to a normal.)
9-1-2. LED Display on P.C. Board (Indoor unit)
1. D501 (Red)
It goes on (Goes on by operation of the main microcomputer) at the same time when the power supply is
turned on.
It flashes with 1-second interval (every 0.5 second): When there is no EEPROM or writing-in operation fails.
It flashes with 10-seconds interval (every 5 second): During DISP mode
It flashes with 2-seconds interval (every 1 second): While setting of function select (EEPROM)
2. D403 (Red)
It goes on when power supply of the remote controller is turned on. (Lights on hardware)
3. D503 (Yellow): Main bus communication
It goes on for 5 seconds in the first half of communication with the central controller.
4. D504 (Green) : Sub bus communication
It flashes for 5 seconds in the first half of communication with the remote controller. (Group master unit)
It flashes with 0.2-second interval (for 0.1 second) for 5 second in the latter half of communication between
master and follower in the Gr indoor unit.
5. D14 (Orange)
It flashes while receiving the serial signal from the outdoor unit. (Hardware)
6. D15 (Green)
It flashes while sending the serial signal to the outdoor unit. (Hardware)