13
Last in rst out:
The indoor unit will execute the last order sent by the central controller, wired controller or remote
controller.
For example, if a low fan speed order is sent rst by the central controller followed by a high fan speed
order by the wired controller, the indoor unit will execute only high fan speed order.
Central:
The central controller enjoys all the functions while the wired & remote controller can only control ON/
OFF function of indoor units.
Lock:
The central controller enjoys all functions while the wired & remote controller cannot control indoor
units.
The parameters can be adjusted according to the needs.
Click on the second icon in the bottom row to select the indoor units that need to be screened as
shown below.
Picture 11
Function operation
English