EasyManua.ls Logo

Carrier RTU Open - User Manual

Carrier RTU Open
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480262-01 Printed in U.S.A. Form 48-50-RTU-01T Pg 1 1-20 Replaces: 48-50LHTCQ-01T
Controls, Start-Up, Operation and
Troubleshooting
48/50FC04-07, 50FCQ, 48/50GC04-06, 50GCQ, 48/50KC04-06, 50KCQ04-06,
48/50HC-4-28, 50HCQ04-12, 48/50LC04-26, 48/50TC07-30, 50TCQ07-24
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SENSOR/ACCESSORY INSTALLATION . . . . . . . . . . 2
Sensors and Accessories . . . . . . . . . . . . . . . . . . . . . 4
User Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Install Analog Sensors . . . . . . . . . . . . . . . . . . . . . . . 11
SUPPLY AIR SENSOR (SAT)
OUTDOOR AIR SENSOR (OAT)
SPACE TEMPERATURE SENSOR (SPT)
SENSOR AVERAGING
CO2 SENSOR(S) (IAQ AND OAQ)
RELATIVE HUMIDITY SENSORS (SPACE OR DUCT
MOUNTED)
Installing Discrete Inputs . . . . . . . . . . . . . . . . . . . . . 13
COMPRESSOR SAFETY
HUMIDISTAT
SINGLE ENTHALPY (OUTDOOR ENTHALPY)
DIFFERENTIAL ENTHALPY
FIRE SHUTDOWN
FILTER STATUS
FAN STATUS
REMOTE OCCUPANCY
IGC OVERRIDE
Communication Wiring-Protocols . . . . . . . . . . . . . . 15
GENERAL
I-VU BUILDING AUTOMATION SYSTEM
•BACNET MS/TP
MODBUS
JOHNSON N2
LONWORKS
LOCAL ACCESS
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
EcoBlue™ Fan Set Up . . . . . . . . . . . . . . . . . . . . . . . 17
Additional Installation/Inspection . . . . . . . . . . . . . . 17
POWER EXHAUST RELAY POWER
•SERVICE TEST
•FAN TEST
HIGH SPEED FAN TEST
COMPRESSOR 1 AND COMPRESSOR 2 TEST
HEAT 1 AND HEAT 2 TEST
DEHUMIDIFICATION TEST
POWER EXHAUST TEST
ECONOMIZER TEST
VFD SPEED TEST
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
SETPOINT
UNIT
•INPUTS
SERVICE CONFIGURATION
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Occupancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
ALWAYS OCCUPIED (DEFAULT)
BACNET SCHEDULE
BAS ON/OFF
REMOTE OCC INPUT
Indoor (Supply) Fan . . . . . . . . . . . . . . . . . . . . . . . . . .22
•AUTO
CONTINUOUS
•ALWAYS ON
FAN OFF DELAY
INDOOR (SUPPLY) FAN STATUS
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Supply Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Economizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Enthalpy Control . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Space Air Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Power Exhaust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Pre-Occupancy Purge . . . . . . . . . . . . . . . . . . . . . . . .24
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Indoor Air Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Dehumidification . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Demand Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Unoccupied Free Cooling . . . . . . . . . . . . . . . . . . . . .25
Optimal Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Fire Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Compressor Safety . . . . . . . . . . . . . . . . . . . . . . . . . .25
Fan Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Filter Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Door Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Remote Occupancy . . . . . . . . . . . . . . . . . . . . . . . . . .26
Linkage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
LINKAGE AIR SOURCE MODES
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . .26
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
REPLACING THE RTU OPEN CONTROLLER
BATTERY
Thermistor Troubleshooting . . . . . . . . . . . . . . . . . . .26
Software Version . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Communication LED's . . . . . . . . . . . . . . . . . . . . . . . .27
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
SAFETY CHAIN ALARM
FIRE/SMOKE SHUTDOWN ALARM
GAS VALVE ALARM
SUPPLY FAN FAILURE
SUPPLY FAN IN HAND
COMPRESSOR STATUS
SPACE TEMP SENSOR
ZS SENSOR
SUPPLY AIR TEMP SENSOR
LOCAL OAT SENSOR
OUTDOOR AIR TEMP SENSOR
SPACE RELATIVE HUMIDITY SENSOR
RTU Open
Multi-Protocol Controller
Factory-Installed Option

Table of Contents

Questions and Answers:

Carrier RTU Open Specifications

General IconGeneral
BrandCarrier
ModelRTU Open
CategoryController
LanguageEnglish

Summary

SAFETY CONSIDERATIONS

ELECTRICAL SHOCK HAZARD WARNING

Warning about electrical shock hazards during service and wiring.

SENSOR INSTALLATION GUIDANCE

Guidance on installing sensors and accessories for the RTU Open controller.

SENSOR AND ACCESSORY INSTALLATION

ANALOG SENSOR INSTALLATION

Instructions for installing various analog sensors like SAT, OAT, and SPT.

COMMUNICATION WIRING AND PROTOCOLS

START-UP AND INITIALIZATION

CONTROLLER CONFIGURATION

SETPOINT CONFIGURATION OPTIONS

Configuration of temperature and humidity setpoints for occupied/unoccupied periods.

UNIT CONFIGURATION SETTINGS

Unit configuration parameters for the RTU Open controller.

INPUT CONFIGURATION OPTIONS

Configuration of various input functions for the RTU Open controller.

OPERATION MODES AND CONTROL

COOLING CONTROL LOGIC

Control logic for cooling operation.

ANALOG SENSOR INSTALLATION

DISCRETE INPUT INSTALLATION

ENTHALPY CONTROL SYSTEMS

SINGLE ENTHALPY (OUTDOOR) OPERATION

Operation and wiring of the outdoor enthalpy sensor for economizer cooling.

DIFFERENTIAL ENTHALPY CONTROL

Control logic and wiring for differential enthalpy sensing.

FIRE SHUTDOWN INPUT CONFIGURATION

COMMUNICATION PROTOCOL DETAILS

START-UP AND SERVICE PROCEDURES

ADDITIONAL INSTALLATION INSPECTIONS

Inspection of accessories and wiring.

SERVICE TEST FUNCTIONALITY

Using service test to verify component operation.

FAN TESTING PROCEDURES

Manual control of the fan output for testing.

COMPRESSOR AND HEAT STAGE TESTING

COMPRESSOR 1 AND 2 TEST PROCEDURES

Testing individual compressor stages for proper operation.

HEAT 1 AND 2 TEST PROCEDURES

Testing individual heat stages for proper operation.

SPECIALIZED UNIT TEST PROCEDURES

DEHUMIDIFICATION TEST OPERATION

Testing the dehumidification relay and modes.

POWER EXHAUST TEST FUNCTION

Manual control of the power exhaust output.

ECONOMIZER TEST FUNCTION

Manual control of the economizer damper position.

VFD SPEED TEST FUNCTION

Testing the VFD supply fan speed output.

CONTROLLER CONFIGURATION PARAMETERS

SETPOINT CONFIGURATION PARAMETERS

Configuration of temperature and humidity setpoints.

UNIT CONFIGURATION PARAMETERS

Unit configuration parameters.

ADVANCED SETTINGS AND INPUT CONFIGURATION

OCCUPANCY SOURCE CONFIGURATION OPTIONS

Method for determining unit occupancy.

INPUT FUNCTION AND TYPE CONFIGURATION

SERVICE CONFIGURATION OPTIONS

UNIT TYPE AND COMPRESSOR STAGES CONFIGURATION

Configuration of unit type and number of cooling stages.

ECONOMIZER AND FAN CONTROL CONFIGURATION

Configuration for economizer existence and fan control type.

OPERATION MODES AND FAN CONTROL

OCCUPANCY CONTROL METHODS

Description of occupancy control methods.

SUPPLY FAN OPERATION MODES

Configuration and operation of the indoor supply fan.

COOLING CONTROL LOGIC EXPLANATION

Control logic for cooling operation.

SUPPLY FAN AND ECONOMIZER OPERATION DETAILS

SUPPLY FAN CONTROL MODE SELECTION

Fan control types: Single, Two Speed, Variable Speed.

ECONOMIZER OPERATION CONDITIONS

Conditions required for economizer to operate.

ECONOMIZER AND AIR QUALITY CONTROL FUNCTIONS

ECONOMIZER CONTROL LOGIC EXPLANATION

Economizer damper positioning based on conditions.

ENTHALPY CONTROL LOGIC EXPLANATION

Using enthalpy sensors for economizer cooling suitability.

SPACE AIR QUALITY CONTROL LOGIC

Control of indoor air quality using CO2 sensors.

POWER EXHAUST AND PURGE OPERATION

POWER EXHAUST CONTROL LOGIC

Control of power exhaust fan based on occupancy or damper position.

PRE-OCCUPANCY PURGE FUNCTIONALITY

Purging the space with outdoor air before occupancy.

HEATING AND INDOOR AIR QUALITY MAINTENANCE

HEATING CONTROL LOGIC EXPLANATION

Control logic for heating operation.

INDOOR AIR QUALITY MAINTENANCE PROCEDURES

Maintaining indoor air quality with optional sensors.

DEHUMIDIFICATION AND DEMAND LIMIT CONTROL

DEHUMIDIFICATION OPERATION MODES

Operation of dehumidification with Humidi-Mizer option.

UNOCCUPIED FREE COOLING AND OPTIMAL START

OPTIMAL START FUNCTIONALITY

Utilizing optimal start for efficient heating/cooling initiation.

SAFETY AND STATUS INPUT CONFIGURATION

COMPRESSOR SAFETY INPUT CONFIGURATION

Configuring compressor safety input for equipment protection.

RTU OPEN CONTROLLER TROUBLESHOOTING

GENERAL TROUBLESHOOTING STEPS

General troubleshooting steps for the RTU Open controller.

RTU OPEN CONTROLLER ALARMS AND FAULTS

AIRSIDE LINKAGE AND PERFORMANCE MONITORING

THIRD PARTY NETWORKING TROUBLESHOOTING

USER INTERFACE MENUS (CONTINUED)

ALARMS MENUS (CONTINUED)

More alarm information and status.

SERVICE TEST MENUS

Menus for performing various service tests on unit components.

ALARMS MENUS

Accessing and viewing controller alarms.

CONFIGURATION POINTS DEFINITIONS

CONFIGURATION POINTS (CONTINUED)

SERVICE TEST SETTINGS DEFINITIONS

Settings for performing various diagnostic tests on unit components.

Related product manuals