CL-5
SERVICE TEST
Service Test test_enable Disable/Enable Disable
Fan Test fan_test Disable/Enable Disable
High Speed Fan Test hi_spd_test Disable/Enable Disable
Compressor 1 Test comp1_test Disable/Enable Disable
Compressor 2 Test comp2_test Disable/Enable Disable
Heat 1 Test heat1_test Disable/Enable Disable
Heat 2 Test heat2_test Disable/Enable Disable
Reversing Valve Test rev_vlv_test Disable/Enable Disable
Dehumidification Test dehum_test Disable/Enable Disable
Power Exhaust Test pexh_test Disable/Enable Disable
Economizer Test econ_test 0-100 %Open 0
VFD Speed Test vfd_spd_test 0-100% or 0-10vdc 0
1 This point is hidden from view when Continuous Occupied Exhaust is enabled.
2 This point is only visible when Fan Control is configured for Two Speed.
3 This point is only visible when Unit Type is configured for HP O/B Ctrl or HP Y1/W1 Ctrl.
4 This point is visible when Fan Control is configured for Variable Speed and not LC WeatherExpert.
5 This point is not visible when unit type is configured for LC WeatherExpert.
6 This point is visible when Unit Type is configured for HP O/B Ctrl.
CONFIGURATION POINTS (CONT)
POINT NAME BACnet OBJECT RANGE DEFAULT ENTRY