35
INPUT CONFIGURATION
RTU Properties
Menu>
Startup Wizard
3 Input 1 Function ai1_function 1=No Sensor
2=IAO Sensor
3=OAQ Sensor
4=Space RH Sensor
IAQ Sensor Properties>
Control Program>
Configuration>
Unit Configuration>
Input Configuration
3 Input 2 Function ai2_function 1=No Sensor
2=IAO Sensor
3=OAQ Sensor
4=Space RH Sensor
No Sensor
IAQ (FIOP CO
2
sensor)
3 Input 3 Function di3_function 1=No Function
2=Compressor Safety
3=Fan Status
4=Filter Status
5=Remote Occupancy
6=Door Contact
Compressor Safety
N/A Input 3 Switch
Configuration
di3_type N/O
N/C
N/C
3 Input 5 Function di5_function 1=No Function
2=Fire Shutdown
3=Fan Status
4=Filter Status
5=Remote Occupancy
6=Door Contact
Fire Shutdown
3 Input 5 Switch
Configuration
di5_type N/O
N/C
N/O
3 Input 8 Function di8_function 1=No Function
2=Enthalpy Switch
3=Fan Status
4=Filter Status
5=Remote Occupancy
6=Door Contact
Enthalpy Switch
3 Input 8 Switch
Configuration
di8_type N/O
N/C
N/O
3 Input 9 Function di9_function 1=No Function
2=Humidistat
3=Fan Status
4=Filter Status
5=Remote Occupancy
6=Door Contact
7=IGC Override
Humidistat
IGC Override (48
Series LC
WeatherExpert
units)
RTU Properties
Menu>
Startup Wizard
3 Input 9 Switch
Configuration
di9_type N/O
N/C
N/O Properties>
Control Program>
Configuration>
Unit Configuration>
Input Configuration
Space sensor type spt_type 1=T55
2=T56 (use for T59)
3=SPT Sensor
4=None
5=ZS Sensor
None
N/A ZS Sensor Binder zs_binder Rnet/Unused Rnet
N/A ZS Zone Temp zs_zone_temp Zone Temp (1-5) Main ZS Sensor
N/A ZS Zone Humidity zs_zone_humidity Zone Humidity (1-5) Main ZS Sensor
N/A ZS Zone CO2 zs_zone_co2 Zone CO2 (1-5) Main ZS Sensor
SENSOR CALIBRATION
Field Assistant Only
Space Temperature lcl_space_temp Properties>
Control Program>
Configuration>
Unit Configuration>
Sensor Calibration
Space Temp
Calibration
spt_offset -9.9 to 10°F 0
Space RH lcl_space_rh 0-100%
Space AQ lcl_space_aq 0-5000ppm
Supply Air
Temperature
lcl_sa_temp -56 to 245°F
Supply Air Temp
Calibration
sat_offset -9.9 to 10°F 0
Outdoor Air
Temperature
lc_oa_temp -56 to 245°F
Outdoor Air Temp
Calibration
oat_offset -9.9 to 10°F 0
Table A — User Interface Menus (cont)
Equipment
Touch Menu
Access
Level
3=ADMIN
2=USER
1=No PW
POINT NAME BACnet Object RANGE DEFAULT
Field Assistant
Menu
APPENDIX A — USER INTERFACE MENUS (CONT)