CL-3
INPUT CONFIGURATION (cont)
Space sensor type spt_type 1=T55
2=T56 (use for T59)
3=SPT Sensor
4=None
5=ZS Sensor
None
ZS Sensor Binder zs_binder Rnet/Unused Rnet
ZS Zone Temp zs_zone_temp Zone Temp (1-5) Main ZS Sensor
ZS Zone Humidity zs_zone_humidity Zone Humidity (1-5) Main ZS Sensor
ZS Zone CO2 zs_zone_co2 Zone CO2 (1-5) Main ZS Sensor
SENSOR CALIBRATION
Space Temperature lcl_space_temp
Space Temp Calibration spt_offset -9.9-10°F 0
Space RH lcl_space_rh 0-100%
Space AQ lcl_space_aq 0-5000ppm
Supply Air Temperature lcl_sa_temp -56-245°F
Supply Air Temp Calibration sat_offset -9.9-10°F 0
Outdoor Air Temperature lc_oa_temp -56-245°F
Outdoor Air Temp
Calibration
oat_offset -9.9-10°F 0
SERVICE CONFIGURATION
Unit Type unit_type 1=Heat / Cool
2=LC WeatherExpert
3=HP O/B Ctrl
4=HP Y1/W1 Ctrl
Heat/Cool (KC, TC, HC, FC,
GC models, and LC sizes
04-06)
LC WeatherExpert (LC sizes
07-26)
HP Y1/W1 Cltl (KCQ, TCQ,
HCQ, FCQ, and GCQ
models)
Compressor Stages
4
comp_stages 1=One Stage
2=Two Stages
One Stage (TC/HC sizes
04-07, and A08-A12, KC/FC
sizes 04-06)
Two Stages (TC/HC sizes
08-30, LC and GC sizes
04-06, FC size 07)
Not Displayed (LC
WeatherExpert sizes 07-26)
Economizer Exists econ_exist No/Yes No (No FIOP)
Yes (FIOP)
Fan Control
5
fan_type 1=Single Speed
2=Two Speed
3=Variable Speed
Single Speed (KC/TC/HC
04-07 and A08-12)
Two Speed (TC/HC sizes
08-30)
Variable (LC sizes 07-26,
and FC/GC sizes 04-07)
VFD Input vfd_in_type 0-10Vdc/2-10Vdc 2-10Vdc (LC sizes 07-26)
0-10Vdc (FC/GC sizes 04-07)
Show VFD Config as vfd_spd_cfg Percentage/Voltage Percentage (LC sizes 07-26)
Voltage (FC/GC sizes 04-07)
IDF Max Speed Voltage max_spd_volt 0-10vdc 10Vdc
IDF Min Speed Voltage min_spd_volt 0-10vdc 5.2Vdc
IDF Heat Speed Voltage ht_spd_volt 0-10vdc 5.2 Vdc
Max VFD Output max_vfd_spd 33-100% 100%
Min VFD Output min_vfd_spd 33-100% 40%
Heating VFD Output heat_vfd_spd 20-100% 100%
Stage 1 SAT Stpt stg_1_sat 45-75°F 57°F
Stage 2 SAT Stpt stg_2_sat 45-75°F 57°F (LC sizes 07-26)
55°F (FC/GC sizes 04-07)
Stage 3 SAT Stpt stg_3_sat 45-75°F 56°F
Reversing Valve Output
6
rev_vlv_type O output type/B output type O output type
Heat Type heat_type Electric/Gas Gas (48 Series Units)
Electric (50 Series Units)
CONFIGURATION POINTS (CONT)
POINT NAME BACnet OBJECT RANGE DEFAULT ENTRY