8
Fig. 8 —Threaded Rod
INSTALLING PANEL
NOTE: Panel is ordered separately.
1. Remove  the  grille  from  the  panel  by  sliding  the  grille
latches toward the center of the panel. 
2. Lift grille to a 45 angle and pull to detach it from panel.
3. Unscrew  the  bolts on  the  4  corners  of  the cover panel.
Remove the cover by loosening the cord. See Fig. 9.
Fig. 9 —Removing Grille from Panel
4. Secure panel (without the grille) onto the unit using M5 x
16 screws and washers. Before tightening the screws, be
sure the panel is flush with the false ceiling. See Fig. 10.
Fig. 10 —Mounting Panel
5. When the panel is secure, insert the grille at a 45 angle
and latch it in place.
Step 4 — Connect Piping
CONDENSATE PIPING  — The  unit  is  supplied  with  a
1
-1
/
4
-inch  OD  drain  connection  to  connect  copper  or  plastic
drain  piping.  Follow  these  recommendations  when  installing
condensate piping:
• Maximum pump lift is 29
-1
/
2
 inches.
• The highest point in the condensate piping should be as
close to the unit as possible. See Fig. 11-13 below.
Fig. 11 —Condensate Piping
Fig. 12 —Condensate Drain Connection
Louver motor
Louver 
motor
Drainage  
pipe joint
Hook
Panel hook
Piping joint
Hook bolt 
Phillips 
screwdriver 
MIN. GRADIENT
2
5
8
TO 3
 
1
4
ft
INSULATION
INDOOR
UNIT
FLEXIBLE DRAIN
CONDENSATE HOSE CLAMP
CONNECTOR
PVC DRAIN
PIPE