Check method
On the wired remote controller, central control remote controller and the interface P.C. Board of the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C. Board) to display the operation
is provided. Therefore the operation status can be known. Using this self-diagnosis function, a trouble or position with error of the air conditioner can be found as shown in the following table.
Check code list
The following list shows each check code. Find the check contents from the list according to part to be checked.
y In case of check from indoor remote controller: See “Wired remote controller display” in the list.
y In case of check from outdoor unit: See “Outdoor unit 7-segment display” in the list.
y In case of check from indoor unit with a wireless remote controller: See “Sensor block display of receiving unit” in the list.
: Lighting, : Flashing, : Goes off
ALT: Flashing is alternately when there are two ashing LED.
SIM: Simultaneous ashing when there are two ashing LED.
Inverter: Compressor / Fan Inverter P.C. Board
Check code Wireless remote controller
Check code name Judging device
Wired remote
controller display
Outdoor unit 7-segment display Sensor block display of receiving unit
Auxiliary code Operation Timer Ready Flash
E01
Communication trouble between indoor unit and remote controller
(Detected at remote controller side)
Remote controller
E02 Remote controller transmission trouble Remote controller
E03
Communication trouble between indoor unit and remote controller
(Detected at indoor unit side)
Indoor unit
E04
Communication circuit trouble between indoor / outdoor unit
(Detected at indoor unit side)
Indoor unit
E06 E06 No. of indoor units in which sensor has been normally received Decrease of No. of indoor units I/F
E07
Communication circuit trouble between indoor / outdoor unit
(Detected at outdoor unit side)
I/F
E08 E08 Duplicated indoor unit addresses Duplicated indoor unit addresses Indoor unit • I/F
E09 Duplicated master remote controllers Remote controller
E10 Communication trouble between indoor unit MCU Indoor unit
E11 Communication trouble between Application control kit and indoor unit
Indoor unit
Application control kit
E12 E12
01: Indoor/Outdoor units communication
02: Outdoor/Outdoor units communication
Automatic address start trouble I/F
E15 E15 No indoor unit during automatic addressing I/F
E16 E16
00: Capacity over
01: No. of connected units
Capacity over / No. of connected indoor units I/F
E18 Communication trouble between header and follower units Indoor unit Indoor unit
E19 E19
00: Header is not detected
02: Two or more header units
Outdoor header units quantity trouble I/F
E20 E20
01: Outdoor unit of other line connected
02: Indoor unit of other line connected
Other line connected during automatic address I/F
E23 E23
Sending trouble in communication between outdoor units
Trouble in number of heat storage units (trouble with reception)
I/F
E25 E25 Duplicated follower outdoor addresses I/F
E26 E26 No. of outdoor units which received signal normally Decrease of No. of connected outdoor units I/F
E28 E28 Detected outdoor unit number Follower outdoor unit trouble I/F
E31 E31 *1 Inverter quantity information Inverter communication trouble I/F
F01 ALT Indoor unit TCJ sensor trouble Indoor unit
F02 ALT Indoor unit TC2 sensor trouble Indoor unit
F03 ALT Indoor unit TC1 sensor trouble Indoor unit
F04 F04 ALT TD1 sensor trouble I/F
F05 F05 ALT TD2 sensor trouble I/F
IM_1115350185.indb 21IM_1115350185.indb 21 26/6/2566 BE 14:5726/6/2566 BE 14:57